Weidmuller WAVE Analog DC Alarm User Manual

Page 5

Advertising
background image

14

Selecting the operating mode

SW 1

Function

1

2

3

4

Channel A High Trip

1

Channel A Low Trip

0

Channel B High Trip

1

Channel B Low Trip

0

FAILSAFE, Channel 1& 2

0

0

NON FAILSAFE, Channel 1& 2

1

1

NON FAILSAFE:

The relay picks up when the alarm is triggered.
The relay drops out when the alarm is triggered.

FAILSAFE:

An alarm is also triggered in the FAILSAFE mode,
if, for example, the operating voltage to the
module fails.

Low trip:

Alarm is triggered if the signal undershoots the
threshold.

High trip:

Alarm is triggered if the signal overshoots the
threshold.

Signal threshold:

Adjustments of the signal threshold (1...90 )% are
made for channel 1 with the potentiometer P1,
and separately for channel 2 via potentiometer P2.

Hysteresis:

Adjustments of the hysteresis (1...90 )% are made
for channel 1 with the potentiometer P3, and
separately for channel 2 via potentiometer P4.

Advertising