background image

17

4.

Mounting

Die The analogue signal isolators are mounted on standard TS 35 rails.

5.

Electrical connection

Warning! For applications with high isolation voltages, take measures to

prevent accidental contact and make sure that there is suffi-
cient distance or insulation between adjacent devices!

5.1 Power supply
approx. 1 W
18…30 Vdc
Voltage supply via cross-connections. Operating carrying capacity of
cross-connection

Յ 2 A (see Cat. No. point 7)

Terminal assignments

1 Current input max. 20 mA
2 Voltage input max. 10 V
3 Input GND
4 Supply voltage + 24 Vdc (cross-connected)
5 Supply voltage 0V (cross-connected)
6 Supply voltage 0V (cross-connected)
7 Relay A contakt 11
8 Relay A contakt 12
9 Relay A contakt 14

10 Relay B contakt 21
11 Relay B contakt 22
12 Relay B contakt 24

Wire cross-section max. 2.5 mm

2

Multi-wire conncection max. 1 mm

2

(two wires with same cross-section)

7 8

10

1 2 3

9

11

12

4

5

6