Weidmuller DC/DC CCC HF - with 3 way separation User Manual
Page 4

14
15
Temperature coefficient
≤ 250 ppm/K from measuring
range
Step response time
≤ 40 µs (typ. 30 µs)
Cut-off frequency (-3 dB)
≥ 15 Hz (typ. 20 kHz)
Coordination of Insulation according to EN 50178, 04.98
Rated Voltage
300 V
Rated surge Voltage
4 kV
Overvoltage category
III
Contamination class
2
Clearance and
creepage distances
≥ 3 mm
Coupling capacity
Input/output/supply
1 nF
Isolation voltage
Voltage endurance
Input/output/to mounting rail
4 kV
eff
/1 min
Connection data
Connection
BLZ/SL
Insulating stripping length
8 ± 0.5 mm
Solid core
0.5 ... 2.5 mm
2
Flexible core
0.5 ... 2.5 mm
2
With ferrules
0.5 ... 1.5 mm
2
EMC specification
according to EN 55011,
class B, group 1
according to EN 50081-1
according to EN 50082-2
General
Voltage supply
24 Vdc ± 25 % (18 ... 30 Vdc)
Power consumption
< 1.5 W at I
out
= 20 mA (at output
0 ... 20 mA, 4 ... 20 mA)
< 1.3 W at I
out
= 5 mA
(at output 0 ... 10 V)
Cross-connection, upper
24 V, max. 2 A
Cross-connection, lower
0 V, max. 2 A
Operating temperature
0 ... +55 °C
Storage temperature
-20 ... +85 °C
Approvals
CE, CSA, UL