14

15

Temperature coefficient

≤ 250 ppm/K from measuring
range

Step response time

≤ 40 µs (typ. 30 µs)

Cut-off frequency (-3 dB)

≥ 15 Hz (typ. 20 kHz)

Coordination of Insulation according to EN 50178, 04.98
Rated Voltage

300 V

Rated surge Voltage

4 kV

Overvoltage category

III

Contamination class

2

Clearance and
creepage distances

≥ 3 mm

Coupling capacity
Input/output/supply

1 nF

Isolation voltage
Voltage endurance
Input/output/to mounting rail

4 kV

eff

/1 min

Connection data
Connection

BLZ/SL

Insulating stripping length

8 ± 0.5 mm

Solid core

0.5 ... 2.5 mm

2

Flexible core

0.5 ... 2.5 mm

2

With ferrules

0.5 ... 1.5 mm

2

EMC specification

according to EN 55011,
class B, group 1
according to EN 50081-1
according to EN 50082-2

General
Voltage supply

24 Vdc ± 25 % (18 ... 30 Vdc)

Power consumption

< 1.5 W at I

out

= 20 mA (at output

0 ... 20 mA, 4 ... 20 mA)
< 1.3 W at I

out

= 5 mA

(at output 0 ... 10 V)

Cross-connection, upper

24 V, max. 2 A

Cross-connection, lower

0 V, max. 2 A

Operating temperature

0 ... +55 °C

Storage temperature

-20 ... +85 °C

Approvals

CE, CSA, UL