Weidmuller WI-I/O 9-L-T: Wireless I/O Transmitter Quick Start Guide v1.7 User Manual

Page 6

Advertising
background image

WI-I/O 9-L Transmitter Unit Quick Start Guide

WI-I/O 9-L Transmitter Unit Quick Start v1.7

page 6 of 8

To reset the default factory configuration:

1. Set the RSSI rotary switch to position 0 using a screwdriver.
2. Power on the WI-I/O 9-L-T transmitter.
3. The WI-I/O 9-L-T transmitter flashes all LEDs at medium flash (i.e. 1.6 Hz).

NOTE

: If the LEDs do not flash, you must repeat steps 1 and 2 until the LEDs flash before

continuing.
4. Set the RSSI rotary switch to another position (i.e. position 1) within 5 seconds.
5. Set the RSSI rotary switch to position 0 within another 5 seconds.
6. The WI-I/O 9-L transmitter lights all LEDs for 2 seconds before returning to normal

operation.

NOTE

: If the LEDs do not light for 2 seconds, you must repeat the process from step 1

until the LEDs light before continuing.
7. You can now link the transmitter and receiver units.

You must reset the transmitter unit to factory defaults (to disable encryption) before linking the

transmitter and receiver units. For more information, see the previous section.

NOTE

: You must complete the linking process in 60 seconds.

To link the transmitter and receiver units:

1. Press and hold down the RSSI Pushbutton on the receiver.
2. Power on the receiver while holding down the RSSI Pushbutton
3. Release the RSSI Pushbutton as soon as the Receiver LEDS flash (within 5 seconds

of powering the receiver).

4. The receiver will flash all LEDs for a maximum 60 seconds while it tries to link to the

transmitter.

5. Power on the transmitter. The transmitter sends a special “Link” message to allow the

receiver to recognise the transmitter.

6. When the units link, the receiver lights all LEDs for 2 seconds before returning to

normal operation.

NOTE

: If the receiver LEDs continue flashing within the 60 seconds, the units are not

linked and you should retry the linking process by powering the transmitter off and on

again. If you exceed the 60 seconds, you must restart the linking process from step 1.
7. You can now bench test your configuration before deploying.

Advertising