2.2 - Power Supply

The WI-MOD-945-E module can be powered from a 9 -
30VDC power supply. The power supply should be rated
at 1 Amp minimum. The positive side of the supply must
not be connected to earth. The supply negative is
connected to the unit case internally. The DC supply may
be a floating supply or negatively grounded.

The power requirements of the WI-MOD-945-E unit are
shown in the following table

12VDC

24VDC

Quiescent

300mA

160mA

TX @100mW

370mA

190mA

TX @ 400mW

410mA

210mA

A Ground Terminal is provided on the back of the module. This Terminal should be connected to the Main Ground point of
the installation in order to provide efficient surge protection for the module (refer to the Installation Diagram)

2.3 - Serial Connections

RS232 Serial Port

The serial port is a 9 pin DB9 female and provides for connection to a
host device as well as a PC terminal for configuration, field testing and for
factory testing. Communication is via standard RS232 signals. The WI-
MOD-945-E is configured as DCE equipment with the pin outs detailed
below.

Hardware handshaking using the CTS/RTS lines is provided. The
CTS/RTS lines may be used to reflect the status of the local unit’s input
buffer. The WI-MOD-945-E does not support XON/XOFF.

Example cable drawings for connection to a DTE host (a PC) or another
DCE hosts (or modem) are detailed above.

DB9 Connector Pin Outs

Pin

Name

Direction

Function

1

DCD

Out

Data carrier detect

2

RD

Out

Transmit Data

– Serial Data Output (from DCE to DTE)

3

TD

In

Receive Data

– Serial Data Input (from DTE to DCE)

4

DTR

In

Data Terminal Ready

5

SG

Signal Ground

6

DSR

Out

Data Set Ready - always high when unit is powered on.

7

RTS

In

Request to Send

8

CTS

Out

Clear to send

9

RI

Ring indicator

Figure 4 - Power Supply

Figure 5 - Serial Cable