Weidmuller WI-MOD-945-E: 900Mhz Wireless Ethernet & Device Server v2.16 User Manual

Page 48

Advertising
background image

Weidmuller Wireless Ethernet Modem & Device Server WI-MOD-945-E User Manual

Page 48

www.weidmuller.com

Rev 2.136

4374

TCP-RTU Connection Status (RS232) inverted

4375

TCP-RTU Connection Status (RS485) inverted

4376

TCP-RTU Modbus Server Connection Status inverted

4377

Multicast Pipe Connection Status inverted

4378-4999

Reserved for future use

Modbus TCP Client (Master) enables the WI-MOD-945-E to
connect to one or more Modbus TCP Servers (Slaves).

All Modbus Master messages are directed to/from the
onboard I/O registers depending on configuration (described
below).

The Modbus TCP Client may also poll Modbus RTU (i.e.
serial) devices connected to either the local serial port or a
remote WI-MOD-945-E serial port by enabling the Modbus
TCP to RTU gateway at the corresponding serial port (see
section 3.10 -

“Serial Port Configuration”).

Modbus TCP Client functionality allows a maximum of 100
mappings to be configured and a maximum of 25 different
Modbus TCP Servers.

Modbus TCP Server (Slave) enables the WI-MOD-945-E to accept connections from one or more Modbus TCP Clients
(Masters).

All Modbus transactions routed to the onboard Modbus TCP Server are directed to/from the onboard general purpose I/O
registers. The Modbus TCP Server is shared with the Modbus TCP to RTU Gateway, so that

the Modbus “Device ID” is

used to determine if a Modbus transaction is to be routed to the onboard Modbus TCP Server or to a Modbus RTU device
connected to the serial port. Care should therefore be taken that all serially connected Modbus devices use a different
Modbus Device ID (i.e. Modbus Slave Address) to the onboard Modbus TCP Server. Up to 32 separate connections to the
Modbus TCP Server are supported.

Modbus RTU (serial) Master functionality is achieved by combining the Modbus TCP Client (Master) and Modbus TCP to
RTU Gateway. Simply specify a Modbus TCP Client (Master) connection to a Modbus TCP Server where the server is the
address of any WI-MOD-945-E with Modbus TCP to RTU Gateway enabled. Care should be taken to ensure that the
Device ID (i.e. Modbus Address) of the serial device is different to the Device ID of the onboard Modbus TCP Server of
the WI-MOD-945-E that the serial device is connected to.

Figure 28 -Modbus TCP

Figure 29 - Modbus

Advertising