Uick, Tart, 3 - quick start – Weidmuller WI-MOD-945-E: 900Mhz Wireless Ethernet & Device Server v2.16 User Manual

Page 29

Advertising
background image

Weidmuller Wireless Ethernet Modem & Device Server WI-MOD-945-E User Manual

Page 29

www.weidmuller.com

Rev 2.136

3.3 - Quick Start

Figure 15 - Quick Start

The WI-MOD-945-E has a Quick Start Configuration option, which will cover most important parameters that are needed
to get an initial connection. This is the first stage of the module configuration. For most applications, no further
configuration is required. For more advanced applications, the other parameters can be changed via the normal
configuration pages after the Quick Start configuration has been saved.

Select “Quick Start” from the Main Menu and then you need to select the following parameters:

Quick Start Configuration

Operating Mode

Access Point or Client. Bridge operation is assumed - for Router
selection, go to the Network page after Quick Start

Default Gateway

This is the address that the device will use to forward messages to remote
hosts that are not connected to any of the local bridged network (Ethernet
or Wireless)

IP Address / Subnet Mask

IP Address and Subnet Mask for your application.

System Address (ESSID)

The system address is a text string 1 to 31 characters in length used to
identifies your system

Radio Encryption

Radio encryption selection - None, WPA-PSK (TKIP), WPA-PSK (AES) or
WPA2

– refer to Security Menu section if WEP or Enterprise encryption is

required.

WPA Passphrase

128bit Encryption keys are internally generated based on the Passphrase
and System Address (ESSID). The Passphrase must be between 8 and
63 characters in length, and must be the same for all WI-MOD-945-E
units in the same system.

The default settings will be shown. If your system is connecting individual devices which are not connected to an existing
Ethernet LAN, then you can use the factory default IP values. If you are connecting to an existing LAN, then you need to
change the IP addresses to match your LAN addresses.

After configuring, select “Save to Flash and Reset”.

Radio Data Rate and Channel will be set to Auto, Radio Transmit Power will be set to maximum and any previous
configuration of unrelated parameters will not be modified, and will still apply.