Rockwell Automation 20B PowerFlex 700 Custom Firmware - Option AE User Manual
Page 4

4
PowerFlex
700VC Custom Firmware
INPU
TS &
OUT
PUTS
Di
gi
tal
Outp
ut
s
381
385
389
[Dig Out1 OnLevel]
[Dig Out2 OnLevel]
[Dig Out3 OnLevel]
Sets the relay activation level for options
10-15 and 58 in [Digital Outx Sel]. Units
are assumed to match the above
selection (i.e. “At Freq” = Hz, “At Torque”
= Amps, “Fan & Pump Ctrl” = Hz).
Default:
Min/Max:
Units:
0.0
0.0
0.0/819.2
0.1
380
560
561
562
[Dig Out1 OffLevel]
[Dig Out2 OffLevel]
[Dig Out3 OffLevel]
Sets the relay de-activation level for
option 58 in [Digital Outx Sel]. Units are
assumed to match the above selection
(i.e. “At Freq” = Hz, “At Torque” = Amps).
These parameters are not used for any
other digital output control options.
Default:
Min/Max:
Units:
0.0
0.0
0.0/819.2
0.1
380
Fi
le
Gr
ou
p
No.
Parameter Name & Description
See User Manual for symbol descriptions
Values
Relate
d
Publication 20B-IN012A-EN-P – July, 2005
P/N 380625-P01
Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in USA.
PowerFlex is a registered trademark of Rockwell Automation, Inc.