Product safety – Rockwell Automation 20B PowerFlex 700 Installation Instructions - Frames 0…6 User Manual
Page 6
 
6
Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Product Safety
ATTENTION: An incorrectly applied or installed drive can result in component 
damage or a reduction in product life. Wiring or application errors, such as, 
undersizing the motor, incorrect or inadequate AC supply, or excessive ambient 
temperatures can result in malfunction of the system.
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts 
and assemblies. Static control precautions are required when installing, testing, 
servicing or repairing this assembly. Component damage can result if ESD 
control procedures are not followed. If you are not familiar with static control 
procedures, reference Guarding Against Electrostatic Damage, publication 
8000-4.5.2 or any other applicable ESD protection handbook.
ATTENTION: The “adjust freq” portion of the bus regulator function is 
extremely useful for preventing nuisance overvoltage faults resulting from 
aggressive decelerations, overhauling loads, and eccentric loads. It forces the 
output frequency to be greater than commanded frequency, while the bus 
voltage is increasing toward a level that causes a fault. However, it can also 
cause either of the following two conditions to occur.
• Fast positive changes in input voltage (more than a 10% increase within 6
minutes) can cause uncommanded positive speed changes. However an 
“OverSpeed Limit” fault (F25) occurs if the speed reaches [Maximum Speed] + 
[Overspeed Limit], (parameters 82 and 83). If this condition is unacceptable, 
action must be taken to 1) limit supply voltages within the specification of the 
drive and, 2) limit fast positive input voltage changes to less than 10%. 
Without taking such actions, if this operation is unacceptable, the “adjust freq” 
portion of the bus regulator function must be disabled (see parameters 161 
and 162).
• Actual deceleration times can be longer than commanded deceleration times.
However, a “Decel Inhibit” fault (F24) is generated if the drive stops 
decelerating altogether. If this condition is unacceptable, the “adjust freq” 
portion of the bus regulator must be disabled (see parameters 161 and 162). In 
addition, installing a properly sized dynamic brake resistor provides equal or 
better performance in most cases.
Important: These faults are not instantaneous. Test results have shown that they 
can take between 2…12 seconds to occur.