Table A Modified Parameters:

Parameter

“AX” Option

PowerFlex 700 VC Standard

55 – Maximum Freq

Min = 5.0 Hz
Max = 82.0 Hz
Default = 82.0 Hz

Min = 5.0 Hz
Max = 420.0 Hz
Default = 130.0 Hz

82 – Maximum Speed

Min = 5.0 Hz
Max = 80.0 Hz
Default = 80.0 Hz

Min = 5.0 Hz
Max = 420.0 Hz
Default = 60.0 Hz

83 – Overspeed Limit

Min = 0.0 Hz
Max = 2.0 Hz
Default = 2.0 Hz

Min = 0.0 Hz
Max = 20.0 Hz
Default = 10.0 Hz