Rockwell Automation 20-COMM PowerFlex 7-Class DPI (Drive Peripheral Interface) Network Communication Adapter User Manual

Page 3

Advertising
background image

3

Step 5

Secure and ground the adapter to the drive by doing the following:

On a PowerFlex 70 drive, fold the Internal Interface cable behind the
adapter and mount the adapter on the drive using the four captive
screws. Use the torque recommended in the drawing.

On a PowerFlex 700, PowerFlex 700H drive or PowerFlex 700S drive,
mount the adapter on the drive using the four captive screws. Use the
torque recommended in the drawing.

X1

X2

Drive

Adapter

Internal Interface Cable
folded behind the adapter
and in front of the drive.

PowerFlex 70 - All Frame Sizes

(Adapter mounts in drive.)

PowerFlex 700 Frames 0 and 1

PowerFlex 700S Frames 0 and 1

(Adapter mounts on door.)

Verify metal ground tab is bent 90°
and is under the adapter before
tightening screw. After tightening
the screw, verify continuity exists
between the head of the screw
and drive ground.

Ground Tab Detail

0.9 N-m

(8.0 lb.-in.)

4 Places

0.9 N-m

(8.0 lb.-in.)

4 Places

PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6

(Adapter mounts in drive.)

Verify metal ground tab is bent 90° and
is under the adapter before tightening
screw. After tightening the screw, verify
continuity exists between the head of
the screw and drive ground.

0.9 N-m

(8.0 lb.-in.)

4 Places

PowerFlex 700H Frames 9 and Larger
PowerFlex 700S Frames 9 and Larger

(Adapter mounts behind HIM panel.)