Mounting clearances wiring, Terminal block specifications – Rockwell Automation 20D PowerFlex 700S Auxiliary Control Power Supply User Manual

Page 2

Advertising
background image

Mounting Clearances

Wiring

To meet CE installation requirements, the following wiring method must be followed.

Input Wiring – Inputs should be wired with two conductor twisted pair wire. If shielded wire is used, shields should not be
connected.

Output Wiring – Outputs should be wired using one of the following options.

A) Less than three meters of shielded two conductor wire with shield connected to ground at power supply end.

B) Three meters or less of unshielded two conductor twisted pair wire with two turns through a 1321-M001 Common

Mode Choke or equivalent. Locate choke near the power supply terminals.

Terminal Block Specifications

Note: Refer to the appropriate drive User Manual for location of the AUX Terminal Block.

Name

Maximum
Wire Size

(1)

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Minimum
Wire Size

(1)

Recommended
Wire Size

(2)

(2) Recommended sizes of 600V, 90°C wire for full load rating.

Torque

Input
Terminal Block

3.5 mm

2

(12 AWG)

0.5 mm

2

(22 AWG)

1.5 mm

2

(16 AWG)

0.4-0.5 N-m
(3.5-4.4 lb.-in.)

Output
Terminal Block

3.5 mm

2

(12 AWG)

0.12 mm

2

(26 AWG)

0.2 mm

2

(24 AWG)

50.8 mm

(2.0 in.)

50.8 mm

(2.0 in.)

50.8 mm

(2.0 in.)

50.8 mm

(2.0 in.)

Customer Supplied

24V DC

PowerFlex 700S

AUX Terminal Block

M4 Grounding Stud

Output Terminal Block

Input Terminal Block

DC 24V / 5A

BR1 B

SHLD

SHLD

V/T2 W/T3

PE R/L1 S/L2 T/L3

AUX IN+ AUX OUT–

75C Cu Wire

6 AWG [10MM

2

] Max.

12 IN. LBS.
1.4 N-M

} TORQUE

WIRE
STRIP

CONTROL

POWER

AUX IN+ AUX OUT–

Shielded Output Cable

300V DC Output Cabling Specifications

Category

Description

Insulation and Temperature Ratings

600V, 90°C

Maximum Cable Length

(1)

(1) See output wiring options above.

3 meters (9.9 feet)