Programming

Set parameter 153 [Control Options], Bit 17 Aux Pwr Sply to “1” to enable operation.

General Specifications

Dimensions

– Dimensions are in millimeters and (inches)

Category

Specification

Electrical

Input:

(1)

(1)The PowerFlex 700S Auxiliary Control Power Supply keeps the drive’s control power operating when drive power is removed. For 575/600
volt drives, where the Auxiliary Control Power Supply is required to start a drive power supply, the input voltage to the Auxiliary Control Power
Supply must exceed 24 volts at the input terminals to ensure the drive power supply will start.

24 Volts +/-10% Isolated, 5 Amps Maximum (Full Load Current)

Output:

300 Volts, 100 Watts Maximum, 0.33 Amps Maximum (Full Load Current)

Fusing:

7.5 Amp ATO Mini Fuse

Grounding:

Case is grounded through GND terminal on Input Terminal Block. Mount to grounded surface or ground via Grounding
Stud. Use 0.2 mm

2

(24 AWG) wire for grounding stud connection.

Power Dissipation:

20 Watts

Environment

Maximum Surrounding
Air Temperature:

0-50 degrees C (32 to 122 degrees F)

Storage Temperature:

–40 to 85 degrees C (–40 to 185 degrees F)

Enclosure:

For UL installations, mount in a NEMA Type 1 enclosure

Relative Humidity:

5 to 95% non-condensing

Shock:

30G peak for 11ms duration (–/+1.0 ms)

Vibration:

0.381 mm (0.015 in.) displacement, 2.5G peak

Other

LED Indicator:

Illuminated LED indicates unit is powered. Darkened LED indicates unit is fully discharged.

Use:

Unit is designed to provide control power to one drive only.

Compatible Drives:

PowerFlex 700S Drives: All voltage classes.