Rockwell Automation 20Y PowerFlex Active Front End in IP20 2500 MCC Style Encl. Fr. 10 Bus Splice Kit User Manual

Page 6

Advertising
background image

6

Rockwell Automation Publication 20Y-IN003A-EN-P - September 2014

PowerFlex Active Front End in IP20 2500 MCC Style Enclosure Frame 10 Bus Splice Kit

Step 6: Connect the MCC bus and PE ground splices in the AFE enclosure to the bus

and ground bars, respectively, in the other enclosure.

a.

Assemble the MCC bus splices to the horizontal bus bars in the
other enclosure using the supplied hardware.
Torque to 300 ±10% in

•lb (33.9 ±10% N•M).

b. Assemble the PE ground splices to the top and bottom PE ground

bus bar connections in the other enclosure using the supplied
hardware.
Torque to 65.0 ±10% in

•lb (7.3 ±10% N•M)

Adjacent Enclosure (Front View)

with Bus Bars to be Connected

to AFE Right-side Splices

AFE Enclosure

(Front View)

Advertising