Rockwell Automation 56RF RFID Square 40x40 mm Transceiver Installation Instructions User Manual

Important: save these instructions for future use

Advertising
background image

Installation and Operating Instructions

Bulletin 56RF RFID Square 40 x 40 mm Transceiver

IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.

This publication does not include all specifications, dimensions, or any special installation considerations.

Refer to the product catalog pages for additional information.

Description

The square transceiver is designed for use with the
Allen Bradley high frequency 13.56 MHz RFID system. This
transceiver is ISO 15693 compliant and can read/write ICODE
tags SLI and SL2, allowing infinite tag configuration options
from various manufacturers. Local LEDs allow for quick visual
diagnosis of module status and read/write status.

Square transceivers have universal mounting capability and
measure 40 x 40 mm. Transceivers can be mounted up to
300 ft (91.4 m) away from the interface module, and tags are
readable from distances up to 3.3 in. (85 mm). This
transceiver has an enclosure rating of IP67 and is designed to
withstand harsh industrial environments.

Features

• 13.56 MHz high frequency RFID solution
• ICODE ISO 15693/ISO 18000-3 M1 Compliant
• Read/write speeds up to 625 B/s
• Transceivers can be mounted up to 300 ft (91.4 m) away

from interface modules

• Built-in LEDs for diagnostics
• Universal mounting
• Reliable performance in harsh environments

Typical Applications

• Asset tracking
• Data acquisition
• Product handling
• Tool management
• Automotive
• Food and pharmaceutical
• Security and entrance

Minimum Distance Between Transceivers

Minimum Distance from Surrounding Metal

Min. 300 mm

Metal

Min.
30 mm

Specifications

➊ No condensation
➋ Range reference for a 50 mm diameter tag

Product Selection

Scanning Area ➌

Note: Ideal tag distance for maximum performance is 30…60 mm.
➌ Referenced for a 50 mm disc tag.

General

Enclosure Rating

IP67

Operating Temperature

-25…+60 °C (-13…+140 °F)

Storage Temperature

-40…+85 °C (-40…+185 °F)

Operating Humidity ➊

35…95% RH

Storage Humidity ➊

25…85% RH

Vibration

10 g at 10…500 Hz

Shock Resistance

50 g

Recommended Sensing Distance ➋

2 in. (50 mm)

Max. Sensing Distance ➋

3.3 in. (85 mm)

Max. Distance from Interface Module

300 ft (91.4 m)

Compliance

CE, cULus, C-Tick

Type of Equipment

Industrial control

Electrical
Supply Voltage

24V DC (-20…+10%)

Max. Current Consumption

100 mA

Tag Compatibility

ICODE tags SLI, SL2
ISO 15693 / ISO 18000-3 M1

Connector

M12 4-pin male

Communication Systems

Half duplex communication system
(RS-485)

Baud Rate (Host)

9600 / 19200 / 38400 / 115200 bps

Frequency

13.56 MHz

Baud Rate (Tag)

26.48 kbit/s

Data Length

8-bit

Description

Cat. No.

Square 40 x 40 Transceiver

56RF-TR-4040

Misalignment

Sensing Distance [mm]

0

100

Side Lobe

Side Lobe

OFF

OFF

OFF

0

-80

-40

40

80

60

30

ON

Advertising