Step 3: Remove the
Existing Fan Starting
Capacitor

1. Cut the cable ties that secure the fan capacitor and fan power wires together.

2. Loosen the screws that secure the fan capacitor wires to the plug-in terminal

block at XC on the fan loss board and remove the wires.

3. Unscrew the fan capacitor from the back of the drive frame and remove the

capacitor.

Step 4: Install the New Fan
Starting Capacitor

Install the new fan capacitor in reverse order of removal as detailed in Step 3:

Remove the Existing Fan Starting Capacitor

above.

XF

XC

M

~

Cooling F

a

n

F

a

n

Su

pply

2

3

0VAC

50/60 Hz

PE

U

3

V

3

3

2

3

1

F

a

n

F

au

lt

U

3

F

V

3

F

Z2F

Z2C

U

3

C

yellow-green

b

l

u

e/grey

b

rown

b

l

a

ck

PE

FNL

S

F

a

n C

a

p

a

citor

=

Disconnect capacitor wires
from terminal block XC

Unscrew capacitor
from drive frame

Fan loss detection
board

Cut cable ties