Rockwell Automation 42DR Intrinsically Safe Sensor User Manual

Page 7

Advertising
background image

7

Installation Wiring Diagrams for Series 5000 Intrinsically Safe Version

10mA Max.

Load

Supply Return

Signal

Return

Power Supply

24V DC 8%

( + )

( -- )

Out

Gnd

Earth Ground

(less than 1 ohm)

In

Gnd

Barrier Bus

Gnd

AB #897H--S140

Out

AB #897H--S120

Gnd

In

Barrier Entity Parameters 

Load Supply

Power Supply

24V DC 8%

Load

Supply Return

( + )

( + )

Out

Gnd

Earth Ground

(less than 1 ohm)

Gnd

In

In

Gnd

In

Gnd

Out

Load

Supply

( +5V DC)

Earth Ground

(less than 1 ohm)

Out

AB #897H--S120

Gnd

In

In

Gnd

Gnd

Out

Barrier Entity Parameters 

Power Supply

42DRA--5500, 42DRU--5500

42DRP--5500, 42DRU--5700

42DTB--5500

NPN Open Collector Connections (Sinking)

(2 Barriers Required)

Class I, II, III, Division 1, Group C, D, E, F, G

Class I, II, III, Division 2, Group A, B, C, D, F, G

Zener Diode Barriers

Power Supply

& Load Circuits

Nonhazardous Location

Hazardous Location

Photoheads

Terminal Base

24V DC 8%

Vmax = 29.5V

Imax = 107mA

Ci = 0F

Li = 0H

AB #897H--S120

Gnd

Load

TTL

Device

Supply Return

( + )

( + )

( + )

( -- )

PNP Open Collector Connections (Sourcing)

(3 Barriers Required)

Vmax = 29.5V

Imax = 107mA

Ci = 0F

Li = 0H

Terminal Base

Photohead

Sink Wiring

Terminal Base

Photohead

Source Wiring

( + )

( 1 )

( -- )

( + )

( 2 )

( 3 )

( -- )

Barrier Bus

AB #897H--S120

Out

Barrier Entity Parameters 

AB #897H--S120

Gnd

Barrier Bus

Gnd

AB #897H--S140

( -- )

Signal

Return

Class I, II, III, Division 1, Group A, B, C, D, E, F, G

Class I, II, III, Division 2, Group A, B, C, D, F, G

PNP Open Collector Connections (Sourcing)

(2 Barriers Required)

Vmax = 29.5V

Imax = 107mA

Ci = 0F

Li = 0H

Terminal Base

Photohead

Source Wiring

( + )

( 2 )

( 3 )

( -- )

Notes

:

Installation must be in accordance with the National Electrical CodeR (NFPA 70, Article 504), ANSI/ISA--RP12.6, and the manufacturer’s instructions.

Barrier entity parameters: Voc 29.5V; Isc 107mA; Ca  Ccable; La  Lcable; recommended barriers are indicated on the above wiring diagram.

If the electrical parameters of the cable used are unknown, the following values may be used: Capacitance -- 60pF/ft.; Inductance -- 0.20H/ft.

Barrier bus must be insulated from other grounded metal. Use DIN Rail Mounting Kit, Allen-Bradley #64--136.

Maximum nonhazardous area voltage must not exceed 250V.

An approved dust tight seal is required for Class II, III applications.

The output circuits of Zener Diode Barriers shall be in separate cables or separated from each other per NEC 504--30.

No revision to drawing without prior UL approval.

Allen-Bradley Control Drawing #133--451(Ver 08)