8

#897H--S120 and #897H--S140 Intrinsic Safety Zener

Diode Barrier Information Specifications

Environmental Conditions

Operating Temperatures

--40 to 122F (--40C to +50C)

Storage Temperature

--40F to 167F (--40C to +75C)

Relative Humidity

5% to 95% noncondensation

Vibration Resistance

Vibration Frequency

55Hz

Vibration Amplitude

+1.5mm (+0.062in)

Shock Resistance

20g

Operational Data, Safety Barrier #897H- S120

Input Voltage—Rated

—Max

+24V

+26V

Internal Resistance—Typical

—Tolerance

302

+16

Replaceable Fuse

#23- 155 Rating

80mA

Leakage Current

Micro A

Short Circuit Protection

Yes

Class

I, II, III

Division

1, 2

Groups

A to G

Operational Data, Safety Barrier #897H- S140

Input Voltage—Rated

—Max

+24V

+26V

Voltage Drop Resulting from

Internal Impedance—Typical

—Tolerance

1V

1V @ < 22mA

2V @ > 22mA

Replaceable Fuse

#23- 156 Rating

100mA

Leakage Current

10A

Short Circuit Protection

Yes

Class

I, II, III

Division

1, 2

Groups

A to G

Mounting Accessories

#63- 112

Plastic Mounting Adaptor for Barriers #897H- S120 and #897H- S140

to fit #64- 134 or other EN50022/DIN46277 Mounting Rail.

#64- 134

1m (3.3ft) prepunched zinc plated and chromated steel Mounting Rail

per EN50022/DIN46277 (TS35)

Description

Intrinsic Safety Zener Diode Barriers #897H--S120 and #897H--S140) are

passive protective interface assemblies to isolate intrinsically safe circuits from

non-intrinsically safe circuits as defined in FM Class No. 3610.

Intrinsically safe connections are suitable for hazardous locations classified as:

Class I, II, III

Division 1 or 2

Groups A, B, C, D, E, F, G.

The Intrinsic Safety Zener Diode Barrier offer economical solutions for

instrumentation and control systems in hazardous locations defined by NEC

Article 500.

Principle of the Replaceable Keyed Fuse Assemblies

For the Intrinsic Safety Zener Diode Barriers #897H--S120 & #897H--S140, the

principle of a keyed fuse assembly has been employed. In case of a fault due to

overvoltage, polarity misconnection or transients, only the protective keyed fuse

assembly needs to be replaced. Disassembly, disconnection of the wiring, or

even disposing of the entire barrier is eliminated, thus providing a very

economical solution for application of Intrinsic Safety Zener Diode Barriers.

The protective fuse is securely embedded in a keyed fuse assembly. This keyed

assembly is coded for a defined fuse rating. Only the properly rated keyed fuse

assembly is able to be inserted in the appropriate barrier.

The replacement of the fuse assembly can be done by the user at the job site.

The barriers do not have to be returned to the manufacturer for replacement.

See Operational Data for #897H--S120 and #897H--S140 in Specifications for

proper Replaceable Fuse selection.

4

(102)

#897H--S120 or #897H--S140

Intrinsic Safety

Zener Diode Barrier

with Replaceable Fuse

3 4

Intrinsic

Safety

Barrier

160mA

160mA

160mA

160mA

1 2

0.5

(12.5)

4

(102)

2.1875 (56)

2.75

(70)

3.75

(93.5)

DIN Rail Mounting Hole Spacing

#64--134 TS35 DIN Mounting Rail

PA--8701(Ver 06)

E

2013 Rockwell Automation, Inc. All rights reserved. Printed in USA.

www.rockwellautomation.com

Power, Control and Information Solutions Headquarters

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel : (1) 414.382.2000, Fax : (1) 414.382.4444
Europe/Middle East/Africa : Rockwell Automation, NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel : (32) 2 663 0600, Fax (32) 2 663 0640
Asia Pacific : Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong , Tel : (852) 2887 4788, Fax : (852) 2508 1846

Publication 42DR--IN001A--EN--P

July 2013

Advertising