Rockwell Automation 45BPD Analog Laser Sensor User Manual

Page 9

Advertising
background image

9

Step 4—Discrete Output Configuration (N.O. / N.C.)

Press the

X

button until the “Nc” LED turns on indicating that this function can be set.

This function can be set to either Normally Open mode or Normally Closed mode by pressing the SET button.

The status indicator LED will turn on when the output is in the normally closed mode, the status indicator LED
will turn off when the output is in the normally open mode.

Press the

X

button to advance to the next setting or press the SET and

X

and buttons simultaneously for 1

second to exit the Teach-In process.

Step 5—Factory Reset

Press the

X

button until the “R” LED turns ON indicating that this function can be set.

The sensor can be reset to the factory settings by pressing the SET button.

The status indicator LED will turn on as long as the SET button is depressed to confirm the sensor has been reset.

Press the

X

button to advance to the next setting or press the SET and

X

and buttons simultaneously for 1

second to exit the Teach-In process.

Exit the Teach-In Menu

After the desired functions are set, press SET and

X

simultaneously for approximately 1 second to save the

settings and exit the Teach-In mode. The sensor will begin normal operation based on these Teach-In settings.

Speed Mode

Average Mode (100 measured valves)

Response

I(mA)

Direction of movement

Time(s)