Step 7: install the series b top air flow plate – Rockwell Automation 20P PowerFlex DC Drive Frame D Series A to Series B Fan Replacement User Manual

Page 7

Advertising
background image

Rockwell Automation Publication 20P-IN074A-EN-P - October 2014

7

PowerFlex DC Drive Frame D Series A to Series B Fan Replacement

Step 6: Install the Series B
Three-Phase Fan Loss
Detection Board

1. Place the new data nameplate label over the existing label to show the new

fan loss detection board terminal names.

2. Install the support for the series B three-phase fan loss detection board.

Use a T20 screwdriver to torque the screws to 1 N•m (9 lb•in).

3. Install the series B three-phase fan loss detection board. Use a T10

screwdriver to torque the screws to 0.7 N•m (6.2 lb•in).

4. Connect the fan cables to terminal blocks TB1 (XF2) and TB2 (XF) on

the

fan loss detection board using the following diagram.

5. Connect three-phase (50/60 Hz), 400…460V AC input power to terminal

block TB3 (XE) on the series B fan loss detection board.

Step 7: Install the Series B
Top Air Flow Plate

Install the series B air flow plate in the reverse order of removal as detailed in
Step 2: Remove the Protective Cover and Top Air Flow Plate on

page 3

.

IMPORTANT

When wiring the external power connection of the three-phase fan loss
detection board, pay attention to the proper phase sequence to obtain the
proper fan direction. See the label on the fan.

32

31

PE

W3

V3

U3

TB3

TB1

TB2

PE

TB

TB

PE

W3F V3F

U3F

Z3F

Y3F

X3F

XF

XF2

XE

FNLS3

31

32

PE

W3

V3

U3

TB

TB

PE

W3F

V3F

U3F

Z3F

Y3F

X3F

Fan F

ault

Fan Supply 3 Phase

400V A

C, 50 Hz

400...460V A

C, 60 Hz

To Fan Motor

W

hit

e

W

hit

e

Ye

llo

w

/Gr

een

Black

Gr

ay

Red

Or

an

ge

Blue

Br

ow

n

Tool size: T10
0.7 N•m
(6.2 lb•in)

Advertising