Step 3: assembling the kit parts – Rockwell Automation 20L PowerFlex 700L Frame 2 DC Bus Bar Conversion Kit User Manual
Page 6

6
PowerFlex® 700L Frame 2 DC Bus Bar Conversion Kit SK-L1-DCBS1-F2
Step 3: Assembling the Kit
Parts
1. Assemble the DC- bus bar to the drive using the two (2) new M5 x 16
mm (0.63 in.) long SEMS screws from the kit, placing the ring lug
between the DC- bus bar and screw head. Tighten to the torque shown in
the drawing. Apply a thin stripe of Torque Seal from each M5 screw
head to the bus bar.
2. Assemble the DC+ bus bar to the drive using the two (2) new M5 x 16
mm (0.63 in.) long SEMS screws from the kit, placing the ring lug
between the DC+ bus bar and screw head. Tighten to the torque shown in
the drawing. Apply a thin stripe of Torque Seal from each M5 screw
head to the bus bar.
GND
SHLD
SHLD
PO
WER
STS
PO
RT
MOD
NET
A
NET
B
SHLD
SHLD
➊
➊
➌
➋
➋
Screw M4 x 12 mm Long
4x (4.0 N-m / 35 lb.-in.)
Screw M5 x 16 mm Long
4x (5.8 N-m / 51 lb.-in.)
Screw M5 x
16 mm Long
DC Bus Bar
Ring Lug
DETAIL SECTION
THROUGH BUS BAR