Step 3: remove the existing cooling fan – Rockwell Automation 20P PowerFlex DC Drive - Frame C Cooling Fan User Manual
Page 6
Advertising
6
PowerFlex® DC Drive - Frame C Cooling Fan
Step 3: Remove the
Existing Cooling Fan
1. The cooling fan terminal block is located below the internal Armature
Circuit Fuses and between the V and W phase AC input terminal bus
bars. Loosen the screws that secure the fan power supply wires to the
terminal block and remove the wires.
2. At the bottom of the drive, remove the two screws that secure the fan to
the drive frame and pull the fan away from the drive.
Phase W bus bar
Terminal C of DC output
Loosen screws and remove wires
Phase V bus bar
Remove screws