PowerFlex® DC Drive - Frame C Cooling Fan

Step 3: Remove the
Existing Cooling Fan

1. The cooling fan terminal block is located below the internal Armature

Circuit Fuses and between the V and W phase AC input terminal bus
bars. Loosen the screws that secure the fan power supply wires to the
terminal block and remove the wires.

2. At the bottom of the drive, remove the two screws that secure the fan to

the drive frame and pull the fan away from the drive.

Phase W bus bar

Terminal C of DC output

Loosen screws and remove wires

Phase V bus bar

Remove screws