2wiring diagrams – Rockwell Automation 42D Series 5000 Blue Line with Analog Output User Manual

Page 2

Advertising
background image

2

Wiring Diagrams

+

2

--

Floating Shield

Terminal Style

Power Base

Cable Style

Power Base

(+) 22--28V DC

Gray

Black

Analog Current Output Connections

Red

(--)

RMÁX = Supply Voltage -- 10V

20mA

(+) 40V DC Max

Current

Sensor

+

2

--

Analog Voltage Output Connections

(--)

Voltage Sensor

R = 3 k Ohm minimum

Floating Shield

Terminal Style

Power Base

Cable Style

Power Base

(+) 22--28V DC

Gray

Black

Red

Analog Output

+

3

1

--

NPN Set Point Output Connections

(--)

Floating Shield

Terminal Style

Power Base

Cable Style

Power Base

(+) 22--28V DC

Orang

e

Black

Red

Load

100mA

Max.

(+) 10--30V DC

(+) 10--30V DC

Blue

Load

100mA

Max.

Note:

Details of connection of Allen-Bradley Series 5000 photoelectric sensors to Allen-Bradley Programmable Controllers can be found in

Publication 42MR-4.0.

Calibration of the Analog Output is done with a Voltmeter or an Ammeter. When calibrating the Voltage Output, connect

the Voltmeter between Terminal 2 (+) and the negative power supply Terminal 1 (--). Select the Voltmeter Scale for 10V

DC. When calibrating the Current Output, install the Ammeter between Terminal 2 (--) and the positive power supply

Terminal (+), or the positive of a separate power supply when used. Select the Ammeter scale for 20mA (DC).

1. With Selector Switches 1 and 2, select Analog Current or Voltage Output.
2. With Selector Switches 3 and 4, select Positive or Negative Slope operation.
3. Set retroreflective target at 0.61m (2ft). Adjust the Analog Output Calibration pot. for 10V DC or 20mA (2%) when in

Negative Slope operation, or to 1V DC or 1mA (10%) when in Positive Slope operation.

4. Set the retroreflective target at the desired range. 4.57m (15ft) maximum, 1.52m (5ft) minimum. Adjust the Sensing

Range Adjustment pot. for 1V DC or 1mA (10%) when using Negative Slope operation or to 10V DC or 20mA (2%)

when using Positive Slope operation.

5. Bring the retroreflective target back to 0.61m (2ft). Re-adjust the Analog Output Calibration pot. for 10V DC or 20mA

(2%) when using Negative Slope operation or to 1V DC or 1mA when using Positive Slope operation if necessary.

6. Place the retroreflective target at the desired range. Re-adjust the Sensing Range Adjustment pot. for 1V DC or 1mA

(10%) when using Negative Slope operation or to 10V DC or 20mA (2%) when using Positive Slope operation if

necessary.

The Analog Output is now calibrated.

Calibration of Setpoint Outputs

1. Place the retroreflective target at the distance where the Setpoint Output A is to come on.
2. Adjust the Setpoint pot. A to turn on Output A at this point. (Red LED turns on.)

3. Place the retroreflective target at the distance where the Setpoint Output B is to come on.
4. Adjust the Setpoint B to turn on Output B at this point. (Green LED turns on.)

Note:

Be aware that in the retroreflective mode, when setting the range beyond 3.35m (11ft), white paper response may

occur between 2.54cm (1in) and 0.3m (1ft).

This completes the calibration of Setpoint Outputs.