Rockwell Automation 20-XCOMM-IO-OPT1 I/O Board Option 20-XCOMM-IO-OPT1 User Manual

Installation instructions, I/o board option 20-xcomm-io-opt1

Advertising
background image

I/O Board Option 20-XCOMM-IO-OPT1

Installation Instructions

These Installation Instructions are provided with the I/O
Board option for use with the External Comms Kit 20-
XCOMM-DC-BASE. This document explains how to install
the I/O board into the kit, and provides board specifications
and I/O wiring details.

This I/O Board option provides additional I/O (6 DC inputs
and 2 relay outputs) for the network — not the drive.

Compatability

To use the I/O board, the installed communication adapter
must be the following hardware series and firmware revision
release or higher:

Important: Even though the 20-COMM-B BACnet MS/TP

and 20-COMM-M Modbus/TCP adapters can
be operated in a 20-XCOMM-DC-BASE
Comms Kit, the adapter’s limitations cannot
support the I/O board option.

Installing the I/O Board

1. Remove J1, 12-position Terminal Block Connector.

2. Insert the black bezel into the base of the light pipe

(

Figure 1

).

3. Carefully align the light pipe assembly over the 8 LED

indicators and snap it into the slots on the board.

4. Set JMP 1 Fault Action Jumper for either Fault

Configurable (FLT position, pins 1-2) or Hold Last State
(HLS position, pins 2-3). See

Figure 1

for details.

5. Carefully align the I/O board socket onto the mating plug

of the Comm Kit’s power supply board while placing the
I/O board onto the three standoffs.

6. Fasten the I/O board to the standoffs using the three

screws supplied with the I/O board.

7. Reinstall J1, 12-position Terminal Block Connector.

8. Fasten the enclosure cover onto the Comm Kit’s base

using the two screws in the cover.

Figure 1 Installing the Optional I/O Board

I/O Wiring

Refer to

Figure 2

for I/O function descriptions for each

terminal point on the I/O connector.

Figure 2 I/O Connector Function Descriptions

Communication Adapter

Required
Hardware
(or higher)

Required
Firmware
(or higher)

20-COMM-E EtherNet/IP

Series B

v3.001

20-COMM-C ControlNet (coax)

Series B

v2.001

20-COMM-Q ControlNet (fiber)

Series A

v2.001

20-COMM-D DeviceNet

Series B

v2.001

JMP1 Fault Action Jumper

HLS (Hold

Last State)

Position

FLT (Fault)

Configurable

Position

1

JMP1 FLT

JMP1 FLT

HLS

HLS

2
3

1

2
3

Light Pipe

Black Bezel

I/O Board

J1

Power Supply
Board
Mating Plug

I/O Board Socket

O2 - NO

O2 - COM

O1 - NC

O1 - NO

O1 - COM

IN1

IN2

IN3

IN4

IN5

IN6

INPUT COM

OUT2

OUT1

3 4

5

6

2

1

9 10 11 12

8

7

Advertising