Figure 3 I/O Wiring Example

Configuring the 20-COMM-* Adapter for I/O

When the optional I/O board is installed and the Comms Kit
is mounted and connected, configure the I/O inputs and
outputs. Refer to the communication adapter User Manual
for complete details.

I/O Board LED Indicators

I/O Board Specifications

Inputs

Outputs

LED Name

State

Description

IN1 (Input 1)

Green

Normal operation, Input 1 ON

Off

Normal operation, Input 1 OFF

Solid
Red

Communication with the 20-COMM-*
adapter has not been established.

Possible Reasons: Wrong adapter/series/
firmware (see table above), or bad
connection.

Flashing
Red

Fault - 20-COMM-* adapter has
experienced an Idle or Comm fault, and the
I/O board is taking its configured fault action
for the outputs.

Possible Reasons: Controller in Stop mode
or powered down, DPI connector
disconnected from drive or drive powered
down, or network connector disconnected
from 20-COMM-* adapter.

Orange OPT1 self-diagnostics failure

IN2 (Input 2)
IN3 (Input 3)
IN4 (Input 4)
IN5 (Input 5)
IN6 (Input 6)

Green

Input * ON

(1)

Off

Input * OFF

(1)

OUT1 (Output 1)
OUT2 (Output 2)

Green

Output * ON

Off

Output * OFF

1 2 3 4 5 6 7 8 9 10 11 12

(1)

Output commons are isolated.

Power Source (AC or DC)

Power Neutral / Common

(1)

Power Neutral / Common

(1)

Power Source (AC or DC)

0 VDC

(-)

24 VDC

(+)

(1)

These LEDs will indicate input status when the IN1 LED is in normal operation
(Green or Off) and communicating with the Comm adapter. If the IN1 LED
indicates a problem (Solid Red, Flashing Red or Orange), these LEDs will be
turned Off and will not indicate input status.

Number of Inputs

6 (single common)

Input Voltage Type

24 VDC source load

Maximum Input Voltage

27 VDC

Maximum Input Current

8 mA (each input)

Guaranteed ON-State Voltage

10 - 27 VDC (3 mA minimum)

Guaranteed OFF-State Voltage 0 - 5 VDC (2 mA maximum)
Reverse Polarity Protected

-30 VDC

Response Time

25 ms + network update time

The I/O board is NOT designed for fast I/O response times. Do NOT use
with input devices that will transition (OFF

J ON J OFF) faster than the

response time. Potential input devices include auxiliary contact inputs
from relays or overloads, pushbuttons, etc.

Number of Outputs

2 relay outputs (individually isolated)

1 - Form C contacts
1 - Form A (NO) contact

Maximum Output
Contact Voltage

27 VDC / 125 VAC

Maximum Output
Contact Current

2A

Expected Contact Life

1,000,000 cycles resistive at < 0.5A
500,000 cycles inductive at < 0.5A

500,000 cycles resistive at 1A
300,000 cycles inductive at 1A

300,000 cycles resistive at 2A
150,000 cycles inductive at 2A

Response Time

25 ms + network update time

The I/O board is NOT designed for fast I/O response times. Do NOT use
with output devices that need to transition (OFF

J ON J OFF) faster

than the response time. Potential output devices include pilot lights or a
contact closure reset to another hardware device.

U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives