3.3.4 Default settings
The LSIG-MM are supplied by AB with the following predefined parameters (Set A and Set B):
#
Protection
On/Off
Thresholds
Time
Curve
T.M.
Trip
1
L
—
1 In
144 s
I
2
t
Off
—
2
S
Off
6 In
50 ms
K
—
—
3
I
On
4 In
—
—
—
—
4
G
Off
0.2 In
0.4 s
K
—
On
5
U
Off
50 %
5 s
Off
6
OT
—
Off
7
Language
—
Engl
8
Mains frequency
—
(1)
9
Sel. Neutral
—
(2)
10
S startup
Off
6 In
100 ms
11
G startup
Off
1 In
100 ms
12
Password
—
0001
13
Measurement interval
—
60 min
14
Iw
Off
3 In
15
MM
On
2.5 In
—
—
—
Note:
(1)
= 50Hz for automatic Circuit-Breakers IEC
60Hz for automatic Circuit-Breakers UL
(2)
= off for 3-pole version
50% for 4-pole version