DIR 1000587R0002 (L3821)

(4)

1.2

Abbreviations and notes

1.2.1 Abbreviations

Abbreviations

Meaning

Battery

Power supply unit

BA

Opening coil

BC

Closing coil

CB

Circuit Breaker

CS

Current Sensor (current transformer)

Dialog

Communication module

HW

Hardware

In

Rated current of the Rating Plug installed in the circuit breaker

LSIG

Protection relay for CB 140G-N/140G-NS/140G-R

LSIG-MM

Protection relay for CB 140G-N/140G-NS

MT

Thermal memory

Relay

also called "protection unit" or "protection release"

RMS

Root mean square value

TC

Trip Coil (opening solenoid)

SW

Software

i-Test

"Info/test" button on the front of the relay

Trip

CB opening, generated by the release

Vaux

Auxiliary power supply

1.2.2 Notes
A. Use the "Belden 3105A"- type two-wire cable for instance (not supplied by AB).
B. Use the "Belden 3106A"- type three-wire cable for instance (not supplied by AB).
C. The unit has a "backup-protection" function; if the first command to the opening solenoid does not immediately open the circuit-breaker (TC

partially faulty), TRIP commands are repeatedly sent until the circuit-breaker opens (providing a Vaux is fitted) or the current disappears (if

self-powered). The "backup" condition can be signalled by configuring the unit relays; using the "YO back" selection, it is possible to command

the "opening coil (YO)" accessory as another opening device when TC does not work.

1.2.3 Compatibility between CB and relay

This table summarizes all possible fitting of the relays and 140G circuit breakers.

CB\Relay

LSIG

LSIG-MM

140G/N/140G-NS x

x

140G-R x x