Contact Cartridges

Contact Cartridges Reconfiguration (N.O. N.C.)

8 -12 lb-in
(.9 - 1.4 N-m)

min - 1 x #18 AWG (.75 mm2)
max - 2 x #12 AWG (4.0 mm2)

7 - 14 lb-in

(.8 - 1.6 N-m)

5/16"

(7.9 mm)

Use Copper Wire Only

14 - 18 lb-in

(1.6 - 2.0 N-m)

Remove front cover.

Remove drive bar.

Loosen screw(s).

Convert contacts
N.O. N.C.

Install contact
cartridge.

1

2

4

5

Tighten terminal
screw(s).

7

6

Install drive
bar

8

2

Install front cover

9

Remove contact
cartridge.

3

Any combination of N.O. & N.C.
red cartridges must be used.
Do not use in Timers or Latches.

Cat. No.

Contact Ratings

Continuous

Contact Ratings

Make / Break

10 A

600V AC

10 A

20 A

Lt. Grey

Black

Lt. Grey

Standard

Overlap

Master

700-CP1

700-CP11Z

700-CPM

35 A

Lt. Grey

Tandem (2 Masters)

700-CPH

Red

Safety (Standard)

700-CPS

10 A

Red

Safety (Master)

700-CMS

20 A

600V AC

NEMA

A600

NEMA

A600

(2) X NEMA

A600

(2) X NEMA

A600

NEMA

A600

(2) X NEMA

A600

600V DC

NEMA

P600

NEMA

P600

(2) X NEMA

P600

(2) X NEMA

P600

NEMA

P600

(2) X NEMA

P600

White

Logic Reed

700-CPR

500ma

@ 150 VDC

25 W (Max)

500ma

@ 150 VDC

25 W (Max)

200ma

@ 30 VDC

6 W (Max)

5 A

600V DC

5 A

10 A

20 A

5 A

10 A

200ma

@ 30 VDC

6 W (Max)

ATTENTION: Do not install the logic reed cartridge in a relay, timer or latch unit that is located next to a
Bulletin 700 Type R, RM, RTC sealed contact relay or other device with a strong magnrtic leakage field.
As erratic contact action could result. Because the logic reeds require very little force to operate. At least
2 standard cartridges are required in the relay to provide maximum mechanical life.

35A Jumper Kit Installation

ATTENTION: Both cartridges must be of the same configuration (N.O. or N.C.) (4 N.C. or 6 N.O.
Jumper Kits Maximum per AC or DC Relay) . If a kit is added to the third deck of an AC Relay, be
sure the enclosure is a 700-N31 Series B which has an electrical tape added inside the cover.
Because of a high inner barrier, Jumper Kits should be used on Series B 700-PT pneumatic timers.

(2)

7 - 14 lb-in

(.8 - 1.6 N-m)

18 - 25 lb-in

(2.0 - 2.82 N-m)

#10 AWG

#10 AWG

8 -12 lb-in

(.9 -1.4 N-m)

B-vertical.ai

1

2

3

4

5

6

7

8

A

B

C

D

E

F

G

H

CONFIDENTIAL AND PROPRIETARY INFORMATION. THIS DOCUMENT

CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF

ROCKWELL AUTOMATION, INC. AND MAY NOT BE USED, COPIED OR

DISCLOSED TO OTHERS, EXCEPT WITH THE AUTHORIZED WRITTEN

PERMISSION OF ROCKWELL AUTOMATION, INC.

BULLETIN 700P INSTALLATION
INSTRUCTION SHEET

10000005242

Sheet

Size

Ver

Of

4

2

B

00

Dr.

Date

- - - - - -

- - - - - -

Advertising