Rockwell Automation 842D Absolute Encoder, DeviceNet Multi-Turn User Manual

Page 2

Advertising
background image

2

Mounting Instructions

1. Be sure to select the proper size flexible coupling clamp to

mate to the encoder shaft, e.g., 845–FC–*–*. See
Encoder Accessories in Sensors catalog.

ATTENTION: Do not rigidly connect
the encoder shaft to the machine; this
will cause premature failure of the
encoder or machine bearings. Always
use a flexible coupling.

Flexible Shaft Couplings

Angle

Parallel

OffĆSet

2. Use the dimension drawings to determine the encoder

mounting hole locations.

3. Slide the flexible coupling onto the shaft, but do not tighten

the set screws.

4. Mount the encoder and tighten with three size M4

mounting screws (not supplied).

5. Center the flexible coupling and tighten the set screws.
6. Rotate the machine slowly and verify that the flexible

coupling is not deforming beyond specifications.

7. Align machine to its mechanical zero or home position.

Remove slotted cover located on the back of the encoder
and press the preset position button to change the position
value to the preset value (the factory preset value is zero).
Replace cover.

Preset

To preset the position of the encoder, remove the slotted cover
from the back of the encoder and press the button inside.

ATTENTION: Pressing the preset position
button results in a change of position
reading. This can cause unexpected
motion which could result in damage to
the product, equipment, or personal injury.

Indicator

LED

Status

Off

Not connected not onĆline

Green Blinking

Active but not allocated by master

Green Steady

Active and allocated by master

Red Blinking

Minor fault and/or connection interrupt

Red Steady

Critical communication fault

Setting the MAC–ID (node address),
Baud Rate and Bus Termination Dip Switches

ATTENTION: Connecting this product
to an operational DeviceNet network
with improperly set DIP switches
usually will cause the entire network to
stop communicating. Baud rate setting
must be the same as the rest of the
network and the MAC–ID must be
different than the rest of the network.

Mac-ID

Preset Position

Button

Baud Rate

Bus

Termination

MAC-ID

DIP-6

DIP-5

DIP-4

DIP-3

DIP-2

DIP-1

Address

2

5

2

4

2

3

2

2

2

1

2

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

...

...

...

...

...

...

...

1

1

1

1

1

1

63

0 = DIP switch is OFF
1 = DIP switch is ON

Baud Rate

DIP-3

DIP-2

DIP-1

Baud rate

X

0

0

125 kBaud

X

0

1

250 kBaud

X

1

0

500 kBaud

X

1

1

125 kBaud

X = don’t care
0 = DIP switch is OFF
1 = DIP switch is ON