Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual
Page 148
Advertising

148
Rockwell Automation Publication 750-IN001N-EN-P - April 2014
PowerFlex 750-Series AC Drives
Figure 88 - Standard Barrel Lugs: Approximate Maximum Dimensions
Wires with appropriate terminals can be bolted to both sides of the L-brackets if
required. Frame 8 drives include two L-brackets per phase, allowing up to four
conductors per phase. Terminals should be attached to the L-brackets using M12
or 0.5 in. diameter bolts, nuts and washers. Bellville spring washers, or equivalent,
are recommended.
Figure 89 - Typical Lug Connection Options
44.5
(1.75)
31.8
(1.25)
127.0
(5.0)
ø 12.7
(0.5)
Left side of L-bracket.
Right side of L-bracket.
Both sides of L-bracket.