Rockwell Automation 193-EE Bul 193 E1 PLUS Overload Relay Application and Installation User Manual

Page 6

Advertising
background image

B

B1

F

G

E1

C

D

A

E2

J

K

øM

H

C

L

Lug Kit

Cat

Overload Relay

Accessories

100-DL180 (3 per kit)

100-DL420 (3 per kit)

100-DL630, -DL860 (3 per kit)

193-EE _ F

193-EE _ G

193-EE _ H

193-EE_ F

193-EE _ G

193-EE _ H

193-EE _ F

193-EE _ G

193-EE _ H

193-EE _ F

193-EE _ G
193-EE _ H

3 Pole

Terminal Kit

Overload

Relay Cat

193-EE _ F

100-D95, -D110

100-D115, -D140, -D180

100-D210, -D250,

-D300, -D420

100-D630, -D860

193-EE _ G

193-EE _ H

Contactor

Cat

100-DTB-180

100-DTB-420

N/A

Finger

Protection

Covers

100-DTC180

100-DTC420

100-DTC860

Current

Adjustment

Shield

193-BC8

193-NREEHZ

193-NREEJZ

193-NREEJZ

193-NREEKZ

193-NREELZ

193-NREEMZ

193-NREENZ

30-150 A
40-200 A

40-200 A
60-300 A

100-500 A

120-600 A
160-800 A

193-EE _ F

193-EE _ G

193-EE _ H

Part Number

Overload Relay

Current Range

Width

A

B1

D

E1

E2

F

G

H

Height

B

Depth

C

Without

Terminal

Covers

With

Terminal

Covers

(Reset)

Replacement E1 Plus Module

120

(4.72)

255

(10.04)

155

(6.10)

336.3

(13.24)

552

(21.73)

385.8

(15.19)

418

(16.46)

915

(36.02)

487.4

(19.19)

311.8

(12.27)

508

(20)

360.8

(14.2)

152.7

(6.01)

120

(4.72)

339.8

(13.38)

418

(16.46)

317.8

(12.51)

152.7

(6.01)

269.3

(10.6)

176.5

(6.95)

156

(6.14)

156

(6.14)

270.7

(10.66)

180

(7.09)

3.6

(.14)

3.6

(.14)

3.6

(.14)

3.6

(.14)

226.3

(8.91)

226.3

(8.91)

384.1

(15.12)

265.2

(10.44)

12.5

(.49)

16

(.63)

52.5

(2.07)

21

(.83)

100

(3.94)

226

(8.90)

130

(5.12)

145

(5.71)

230

(9.06)

180

(7.09)

J

K

øM

135

(5.31)

22.3

(.88)

108

(4.25)

109

(4.29)

140

(5.51)

23.5

(.93)

8 - 5.6

(8 - .22)

100

(3.94)

145

(5.71)

135

(5.31)

22.3

(.88)

8 - 5.6

(8 - .22)

8 - 13

(8 - .51)

8 - 6.5

(8 - .26)

Table 4 High fault short circuit ratings, using Bul. 140M, circuit breakers, per UL508 and CSA 22.2 No.14

Table 5 High fault short circuit ratings, using Bul. 140U, circuit breakers, per UL508 and CSA 22.2 No.14

PN-39921
DIR 10000044940 (Version 03)

Printed in U.S.A.

At 480V

At 600 V

EEHF

100-D140

140

65

30

140M-J8P-D20

200

EEJF

100-D180

180

65

30

140M-J8P-D20

200

EEKG

100-D210

210

65

30

140M-J8P-D25

250

EEKG

100-D250

250

65

30

140M-K8P-D40

400

EEKG

100-D300

300

65

30

140M-K8P-D40

400

EELG

100-D420

420

65

30

140M-L8P-D60

600

Circuit Breaker Cat.

No.

Max. Circuit Breaker

Current (A)

193

E1 Plus Cat. No.

Contactor Cat.

No.

Max. starter

FLC (A)

Max. available fault current (kA)

At 480V

At 600 V

EEHF

100-D140

140

65

25

140U-J*C3-D20

200

EEJF

100-D180

180

65

25

140U-J*C3-D20

200

EEKG

100-D210

210

65

25

140U-J*C3-D25

250

EEKG

100-D250

250

65

25

140U-K*C3-D40

400

EEKG

100-D300

300

65

25

140U-K*C3-D40

400

EELG

100-D420

420

65

25

140U-L*C3-D60

600

Circuit Breaker Cat.

No.

Max. Circuit Breaker

Current (A)

193

E1 Plus Cat. No.

Contactor Cat.

No.

Max. starter

FLC (A)

Max. available fault current (kA)