PN-46047 10000054881 Ver 00 October 2009

10

SensaGuard

TM

Installation Instructions

Unit Response Time (does not include safety relay response time)

Note: Refer to Technical Specifications for Certification information and ratings.

Yel

Red

White

Gray

Pink

Blue

24V DC

Power

Supply

1606

Sensor 1

+24

RT

Sensor 2

Brown

Brown

Gray

Pink

White

Yel

Red

Blue

Sensor 3

Brown

Yel

Red

White

Gray

Pink

Blue

A1

S21

S11

41

33

23

13

S12

S52

42

34

24

14

A2

S34

S22

440R-N23127

Actuator 1

Actuator 2

Actuator 3

Initial Conditions:

All actuators are in sensing

distance.

Actuator 1 is moved out of

sensing range.

Sensor 2 drops the 24 volts

(red and yellow) from Sensor 1

OSSD outputs.

Green LED flashes.

Sensor 3 drops the 24 volts

(red and yellow) from Sensor 2

OSSD outputs.

Green LED flashes.

0 ms

54 ms

72 ms

90 ms

Actuator 1 is out of sensing

range.

Actuator 2 and 3 are in

sensing range.

Actuator 1 is moved into sensing

range.

Sensor 1 OSSD outputs are

energized.

Sensor 2 OSSD inputs (red and yellow)

transition to 24V DC from Sensor 1

OSSD outputs.

Sensor 2 OSSD outputs are energized

Sensor 3 OSSD inputs (red and

yellow) transition to 24V DC from

Sensor 2 OSSD outputs.

Sensor 3 OSSD outputs are

energized.

0 ms

360 ms

378 ms

396 ms

OFF

ON