Learning a new actuator, Sensaguard, 18 mm plastic barrel installation instructions 7 – Rockwell Automation 440N SensaGuard 18 mm Plastic Barrel Unique Coded Installation Instructions User Manual

Page 7

Advertising
background image

PN-46045 10000054879 Ver 00 October 2009

SensaGuard

TM

18 mm Plastic Barrel Installation Instructions 7

During the Program Locking Stage, perform the following steps:

a.

Remove the actuator from the sensing field, until the "Status/Diag" LED changes to
solid Red.

b.

Replace the actuator back into the sensing field and the "Status/Diag" LED will
continue blinking Green (# of learns left).

Note:

The program locking sequence must be completed within the 15 second
program locking window.

5. Ready state: "Status/Diag" LED solid Green

6. Learn is complete

Learning a new actuator:

To learn a replacement actuator; bring the actuator to be taught into the sensing range of
the safety switch.

The learn sequence is same as the sequence for commissioning the first actuator.

Note:
A sensor can be locked so it can not learn another actuator by removing the actuator
from the sensing field during the 15 sec "Program Complete" sequence.

A sensor can not re-learn a previously learned actuator or a standard SensaGuard actuator.

Unique Coded Diagnostic:
Error codes for learning process - Repeat until unit is power cycled

Status/Diag LED - Flashes (4Hz)

Error Code

Green

OSSD inputs not valid

Red-Red-Red-Green

Can not learn a standard
SensaGuard Actuator

Red-Red-Red-Green-Green

Actuator already learned

Red-Red-Red-Green-Green-Green

Bad RFID; Target moved out of
range

Red-Red-Red-Green-Green-Green-Green

Exceeded learning 8 actuators

Red-Red-Red-Green-Green-Green-Green-Green

Unit locked: Can not learn
another actuator