Rockwell Automation 509 Full Voltage Starter - Size 8 (Series B Construction) User Manual
Page 2
 
Page 2 of 10
BULLETIN
505 z 509
coil retaining spring; third, loosen the four captive 
screws holding down the coil cover; and fourth, slide 
off the coil cover. The cross bar assembly, as one 
unit, is then lifted out. Disassembly of all parts of the 
cross bar assembly is easily accomp-lished by 
loosening all the nuts and screws on the push rod 
assemblies. 
 
MAGNET ARMATURE ASSEMBLY – The magnet 
armature is laminated and is mounted on the 
armature plate with a rubber pad to absorb shock 
and prolong life. To remove the magnet armature 
assembly, loosen the lock nut at the lower end of the 
push rods. Note – Removal of the magnet 
armature assembly will probably cause the push 
rod shims to fall free. Be sure that upon 
replacing the magnet armature assembly, the 
push rod shims are placed in the same position, 
so that consistent overtravel may be maintained. 
Take out the retaining blocks located on each side of 
the magnet armature. Force the armature plate 
through the armature, thereby isolating the magnet 
armature. Note - The armature pad, spacer, and 
retainer must be replaced in the same order. For 
correct replacement, refer to the exploded view 
on Page 3. 
 
MAGNET YOKE
–
The magnet yoke is laminated
and mounted on an aluminum base casting. The 
pressure molded coil is mounted with the yoke 
projecting into the openings of the coil so that the 
coil slides out with the magnet yoke. 
 
 
OPERATING COIL
–
Unique high-pressure results
in a coil protected against mechanical damage and 
the corrosive effects of atmospheric conditions and 
protects the coil against swelling when subjected to 
over-voltage. Very little trouble can be expected 
from the operating coils. 
 
 Removing the coil is a simple operation that is 
easily performed from the front. First, remove the 
coil terminal cover; second, detach the coil leads; 
third, loosen the two 
 
screws located on the coil retaining spring; and 
fourth, slacken the four captive screws holding down 
the coil cover. The coil cover is then lifted out from 
the font. Now remove the operating coil and magnet 
yoke and detach the yoke from the coil. 
 
 To replace the operating coil, first insert the 
magnet yoke into the operating coil. After this has 
been accomplished, insert both the operating coil 
and the magnet yoke, as a unit, into the switch unit 
securely. Now replace the coil cover into the switch 
unit, but do not tighten the screws on the coil 
retaining spring. Be sure to place the auxiliary 
contact operating lever into the auxiliary contact 
actuator fastened to the cross bar. 
(See instructions
on page 3.)
Tighten the coil retaining spring screws
and the four captive screws on the coil cover. 
Restore the coil leads and put back the coil terminal 
cover. 
 
 
 
 
Coil Current
(Amperes)
Coil
Number
volts
Inrush sealed
120 17.6
.392
208 10.2
.226
240 8.8
.196
480 4.4
.093
107D206
(90V DC)
600 3.5
.078
 
 
NOTE
–
Given values are input current (amperes)
into the control transformers with 120 volt, 60 Hz 
secondary. 
 
 
 
CONTROL PANEL 
-
All auxiliary equipment –
capacitor, rectifier, resistors, contact protector, 
terminal blocks and control transformer (when used) 
– is mounted in a metal cabinet. The cabinet is 
normally mounted below the starter, but may be 
mounted separate from the starter. The cabinet 
(when below starter) is mounted on rubber 
grommets to absorb heavy shock during opening 
and closing of starter. The control panel has a 
hinged cover which can be swung out for inspection 
or to check wiring of auxiliary equipment. 
 
 
BULLETIN 1495 AUXILIARY CONTACTS – 
Provisions are made for two auxiliary contacts in 
addition to the one which is required for the 
economizing action. Each auxiliary contact provides 
two independent circuits, either of which can be set 
as normally open and normally closed, depending 
on the circuit requirements. (
See Instructions - Page 6.
)
 
 
 
 
 
Operating Coil