Default input/output configuration, Variable input/output configuration – Rockwell Automation 150 SMC-Flex User Manual User Manual
Page 111

Communications
7-7
Default Input/Output Configuration
The default configuration for I/O is 4 bytes in and 4 bytes out (TX =
4 bytes, RX = 4 bytes). The total size may very when used with a
communication card. The default configuration is arranged according
to the following table.
➊
The feedback word is always Current in Phase A
➋
The reference word is not used with the SMC-Flex, however the space must be reseverd
Note: The total size produced or consumed may vary, depending on
the communication card being used. For more information,
refer to the User Manual for the communication card.
Variable Input/Output
Configuration
The SMC-Flex supports 16-bit DataLinks. Therefore, the device can
be configured to return additional information. The I/O message size
depends on how many DataLinks are enabled. The following table
summarizes the I/O data sizes.
To configure DataLinks, refer to Configuring DataLinks on
page 7-10.
Table 7.E
Produced Data (Status)
Consumed Data (Control)
Word 0
Logic Status
Logic Command
Word 1
Feedback
➊
Reference
➋
Table 7.F
Rx
Size
Tx
Size
Logic Status/
Command
(16-bit)
Reference/
FeedBack
(16-bit)
DataLinks
A
B
C
D
4
4
x
x
8
8
x
x
x
12
12
x
x
x
x
16
16
x
x
x
x
x
20
20
x
x
x
x
x
x