Typical misalignment curve, Typical wiring diagram diagnostic, Sensaguard – Rockwell Automation 440N SensaGuard 18 mm Stainless Steel Barrel Installation Instructions User Manual
Page 5

Typical Misalignment Curve
18 mm Unit with 18 mm Target
Note: There must be a minimum spacing of 4 mm (0.157 in) if actuator and sensor face approaches
laterally. This will prevent false triggering due to the side lobe areas.
Typical Wiring Diagram
Diagnostic
Unit Indicators (per IEC 60073)
State
Status
Troubleshooting
Off
Not Powered
NA
Device Output
Red
Not Safe, OSSD not active
NA
LED
Green
Safe, OSSD active
NA
Green flash
Power up test or OSSD
Check 24V DC or OSSD inputs
inputs not valid
(yellow and red wire)
Red Flash
1 Hz Flash Recoverable Fault
Recoverable fault —check OSSD
4 Hz Flash Non-recoverable Fault
outputs are not shorted to GND,
24V DC or each other. Cycle power.
SensaGuard
TM
18 mm Stainless Steel Barrel Installation Instructions 5
Misalignment
Sensing Distance
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-15 -14-13 -12-11-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Side Lobe
Side Lobe
Assured Sensing
Distance
OFF
OFF
OFF
ON
Note: Refer to Technical Specifications for Certification information and ratings.
PA-75056-181, Ver 05 March 2012
Description
Plastic
8-Pin Micro (M12)
Grey
Safety A
Red
Safety A+
Pink
Safety B
8-Pin Cordset
Yellow
Safety B+
889D-F8AB-*
White
Aux A
or cable version
Brown
24V DC+
Blue
Gnd / 0V
Green
N/A
* Replace symbol with 2 (2m), 5 (5m) or 10 (10m) for standard cable lengths.
2-24V DC+
1-Aux A
7-0V
6-Safety B
3-N/A
8-Safety A+
4-Safety B+
5-Safety A