Typical misalignment curve, Typical wiring diagram diagnostic, Sensaguard – Rockwell Automation 440N SensaGuard 18 mm Stainless Steel Barrel Installation Instructions User Manual

Page 5

Advertising
background image

Typical Misalignment Curve

18 mm Unit with 18 mm Target

Note: There must be a minimum spacing of 4 mm (0.157 in) if actuator and sensor face approaches
laterally. This will prevent false triggering due to the side lobe areas.

Typical Wiring Diagram

Diagnostic

Unit Indicators (per IEC 60073)

State

Status

Troubleshooting

Off

Not Powered

NA

Device Output

Red

Not Safe, OSSD not active

NA

LED

Green

Safe, OSSD active

NA

Green flash

Power up test or OSSD

Check 24V DC or OSSD inputs

inputs not valid

(yellow and red wire)

Red Flash

1 Hz Flash Recoverable Fault

Recoverable fault —check OSSD

4 Hz Flash Non-recoverable Fault

outputs are not shorted to GND,

24V DC or each other. Cycle power.

SensaGuard

TM

18 mm Stainless Steel Barrel Installation Instructions 5

Misalignment

Sensing Distance

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

-15 -14-13 -12-11-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Side Lobe

Side Lobe

Assured Sensing

Distance

OFF

OFF

OFF

ON

Note: Refer to Technical Specifications for Certification information and ratings.

PA-75056-181, Ver 05 March 2012

Description

Plastic

8-Pin Micro (M12)

Grey

Safety A

Red

Safety A+

Pink

Safety B

8-Pin Cordset

Yellow

Safety B+

889D-F8AB-*

White

Aux A

or cable version

Brown

24V DC+

Blue

Gnd / 0V

Green

N/A

* Replace symbol with 2 (2m), 5 (5m) or 10 (10m) for standard cable lengths.

2-24V DC+

1-Aux A

7-0V

6-Safety B

3-N/A

8-Safety A+

4-Safety B+

5-Safety A