Dimensions / Abmessungen / Dimensions / Dimensioni / Dimensiones
Depending on the confi guration, a one-
time interruption of the emergency-stop 
circuits (startup test) can be required 
after the unit has been powered up. 
On interruption of the emergency-stop 
circuits, the status output switches off 
immediately, while the safety outputs 
switch off when the preset delay ends. 
The time delay function of the 
MSR38D/DP is protected against time 
extension. While the delay period is 
active, it is not possible to interrupt the 
delay, restart or retrigger the system. The 
desired off delay value is set by shorting 
terminals Y11/12/13 with S11/12, in 
combinations given in the delay settings 
table. The delay time has a direct eff ect 
on the response time of the system. A 
change in the delay setting becomes 
eff ective only after the power supply to 
the unit has been turned off and then 
on again. After any change in the delay 
setting, the new delay time should 
be verifi ed. If both channels are to be 
controlled with the same signal (single 
channel operation or without cross 
fault detection), terminals Y41 and A1 
must be shorted. For feedback circuit 
monitoring, terminals A1 (+24 V) and Y2 
must be shorted, either through N.C. 
contacts of a contactor, or by a jumper. 
By continuously scanning all inputs, 
faults or confi guration changes occurring 
during operation are detected, resulting 
in immediate tripping action.
Je nach Konfi guration, kann ein 
einmaliges Öff nen der Not-Halt Kreise 
nach Anlegen der Versorgungsspan-
nung angefordert werden (Anlauftest). 
Bei Unterbrechung der Not-Halt Kreise 
schaltet der Meldeausgang sofort ab und 
die Sicherheitsausgänge nach Ablauf der 
eingestellten Zeit ab. Die Zeitfunktion 
des MSR38D/DP ist sicher bezüglich 
Zeitverlängerung. Zeitunterbrechung, 
Neustart oder Retriggern des Systems 
während des Zeitablaufes ist nicht 
möglich. Die gewünschte Rückfall-
verzögerung kann durch Brücken der 
Klemmen Y11/12/13 nach S11/21 gemäß 
Zeittabelle konfi guriert werden. Die 
konfi gurierte Zeitverzögerung hat einen 
direkten Einfl uss auf die Reaktionszeit des 
Systems. Die Übernahme der Konfi gura-
tion erfolgt erst nach dem Power-up des 
Gerätes. Nach jeder Neukonfi guration 
ist die eingestellte Zeit zu überprüfen. 
Sollen beide Kanäle mit gleichem 
Signal betrieben werden, ist Y41 mit A1 
zu verbinden (Betriebsart einkanalig 
oder ohne Querschlusserkennung). Zur 
Rückführkreisüberwachung können 
Öff nerkontakte von Schützen oder 
Kontakterweiterungsmodulen zwischen 
A1 (+24 V) und Y2 eingebunden werden. 
Sonst ist Y2 mit A1 zu brücken. Durch 
die dynamische Abfrage aller Eingänge 
führen Fehler oder Änderungen der 
Konfi guration während des Betriebes zur 
sofortigen Abschaltung.
contrôlé (branché entre les bornes 
A1-S34), par détection du front des 
impulsions. Suivant la confi guration, une 
coupure temporaire des circuits d‘arrêt 
d‘urgence (test au démarrage) peut 
être requise après mise sous tension 
de l‘unité. Lorsque les circuits d‘arrêt 
d‘urgence sont interrompus, la sortie 
indiquant l‘état du module MSR38D/DP 
est immédiatement désactivée, tandis 
que les sorties de sécurité le sont à la 
fi n de la temporisation prédéfi nie. La 
fonction de temporisation du MSR38D/
DP est protégée contre les prolonga-
tions. Lorsque la temporisation est active, 
il n‘est pas possible de l‘interrompre ni 
de redémarrer ou de réenclencher le 
système. Pour défi nir la temporisation 
souhaitée, il faut court-circuiter les 
bornes Y11/12/13 et S11/12 suivant les 
combinaisons données dans le tableau 
des réglages de temporisation. La durée 
de la temporisation aff ecte directement 
le temps de réponse du système. Une 
temporisation modifi ée prendra eff et
seulement après la remise sous tension 
de l‘alimentation du module. Après toute 
modifi cation de la temporisation, le nou-
veau délai doit être vérifi é. Si les deux ca-
naux doivent être contrôlés par le même 
signal (fonctionnement sur un seul canal 
ou sans détection croisée des défauts) les 
bornes Y41 et A1 doivent être mises en 
court-circuit. Pour le contrôle des circuits 
par rétroaction, les bornes A1 (+24 V) et 
Y2 doivent être mises en court-circuit 
par les contacts N.F. d‘un contacteur ou 
par un cavalier. Le contrôle permanent 
de toutes les entrées permet de détecter 
tous les défauts ou modifi cations de 
confi guration se produisant pendant 
le fonctionnement et de provoquer un 
déclenchement immédiat.
A seconda della confi gurazione è 
possibile richiedere un‘apertura unica 
dei circuiti di ARRESTO-EMERGENZA 
dopo l‘inserimento della tensione di 
alimentazione (test di avviamento). In 
caso di un‘interruzione dei circuiti di 
ARRESTO-EMERGENZA, dopo la scadenza 
del periodo impostato, viene disattivata 
immediatamente l‘uscita di segnalazione 
e le uscite di sicurezza. La funzione del 
tempo dell‘unità MSR38D/DP è sicura per 
quanto riguarda il prolungamento dei 
tempi. Non è possibile un‘interruzione dei 
tempi, un riavvio o una rieccitazione del 
sistema durante la scadenza del tempo. 
È possibile confi gurare il ritardo dello 
scatto cavallottando i morsetti Y11/12/13 
in S11/21 secondo la tabella dei tempi. 
Il ritardo di tempo confi gurato infl uenza 
direttamente il tempo di reazione del sis-
tema. La confi gurazione viene applicata-
solo dopo il Power-up dell‘apparecchio. È 
necessario controllare il tempo impostato 
dopo ogni nuova confi gurazione. Nel caso 
in cui ambedue i canali dovessero essere 
utilizzati con lo stesso segnale, occorre 
collegare Y41 con A1 (modo operativo ad 
un canale o senza riconoscimento di cor-
tocircuito trasversale). Per il monitoraggio 
del circuito di rimessa è possibile installare 
contatti di apertura di contattori o moduli 
di estensione contatti fra A1 (+24 V) e Y2. 
Altrimenti occorre cavallottare Y2 con A1. 
Mediante l‘interrogazione dinamica di tut-
ti gli ingressi eventuali errori o modifi che 
della confi gurazione durante l‘esercizio 
provocano un immediato disinserimento.
En función de la confi guración puede soli-
citarse una apertura única de los circuitos 
de parada de emergencia, después de 
conectar la tensión de alimentación 
(prueba de arranque). Con la interrupción 
de los circuitos de parada de emergencia 
se desconecta la salida de señalización in-
mediatamente y las salidas de seguridad 
una vez transcurrido el tiempo ajustado. 
La función de temporización del MSR38D/
DP es segura respecto de la prolongación 
de tiempo. No es posible la interrupción 
del tiempo, el reinicio o la activación de 
la función retrigger (volver a activar) del 
sistema durante el transcurso del tiempo. 
Puede confi gurarse la caída retardada 
deseada mediante puentes de los bornes 
terminales Y11/12/13 hacia S11/21 
conforme a la tabla de tiempos. El retraso 
confi gurado tiene una infl uencia directa 
sobre el tiempo de reacción del sistema.
La aceptación de la confi guración no se 
produce hasta el encendido del aparato. 
Debe comprobarse el tiempo ajustado 
después de cada nueva confi guración. Si 
se desea accionar los dos canales con la 
misma señal, debe conectarse Y41 con 
A1 (modo de funcionamiento con un 
canal o sin detección de derivación). Para 
el control del circuito de retorno pueden 
integrarse los contactos de apertura de 
contactores o módulos de ampliación 
de contactos entre A1 (+24 V) e Y2. De lo 
contrario debe puentearse Y2 con A1. A 
través de la consulta dinámica de todas 
las entradas, llevan errores o modifi cacio-
nes de la confi guración durante el funcio-
namiento a la desconexión inmediata.
The safety relay MSR38D/DP can be used 
in safety circuits according to DIN EN 
60204-1/VDE 0113 part 1. Based on the 
operation mode and wiring the below 
mentioned safey requirements are 
achievebale in maximum. 
Specifi cations are applicable only if the 
safety function is demanded at least 
once within 6 months. All diagnostic 
test are carried out at least before next 
demand. The mission time (TM) for the 
proof test interval (PTI) is adopted.
Components failure rates according to 
SN29500.
Das Sicherheits-Relais MSR38D/DP kann 
in Sicherheitsstromkreisen nach DIN 
EN 60204-1/VDE 0113 Teil 1 eingesetzt 
werden. Je nach äußerer Beschaltung sind 
max. die unten aufgeführten Anforderun-
gen zu erreichen.
Die Anforderungen der aufgeführten 
Normen werden erfüllt, wenn die 
Sicherheitsfunktion mindestens einmal 
innerhalb von 6 Monaten betätigt wird. 
Alle Diagnosetests werden spätestens bis 
zur nächsten Anforderung ausgeführt. 
Als Intervall für Wiederholungsprüfungen 
(PTI) wird die Nutzungsdauer (TM) ange-
nommen, Fehlerraten der Komponenten 
gemäß SN29500.
Le relais de sécurité MSR38D/DP peut 
être utilisé sur des circuits de sécurité 
conformément à la norme DIN EN 60204-
1/VDE 0113 partie 1. En fonction du mode 
d‘exploitation et du câblage, les spécifi -
cations en matière de sécurité ci-dessous 
peuvent êter suivies dans leur intégralité. 
Les spécifi cations ne s‘appliquent que si 
les actions de sécurité sont demandées au 
moins fois tous les 6 mois. Tous les essais 
de diagnostic sont entrepris au moins 
avant la requête suivante. La période de 
mission (PM), en ce qui concerne l‘interval 
des essais (IE), est adoptée.
Les pannes des composants sont classées 
en conformité avec la norme SN29500.
Il relè di sicurezza MSR38D/DP può essere 
usato in circuiti di sicurezza secondo DIN 
EN 60204-1/VDE 0113 parte 1. Sulla base 
del modo di funzionamento e il cablaggio 
i requisiti di sicurezza sotto indicati sono 
realizzabili in condizioni di massimo. 
Le specifi che sono valide soltanto se la 
funzione di sicurezza viene richiesta al-
meno una volta ogni 6 mesi. Tutti i test di 
diagnostica sono eseguiti almeno prima 
della richiesta successiva. È adottato il 
tempo di missione (TM) per l‘intervallo del 
test di prova (PTI).
Frequenza guasti componenti secondo 
SN29500.
El relé de seguridad MSR38D/DP puede 
usarse en circuitos de seguridad según la 
norma DIN EN 60204-1/VDE 0113 parte 1. 
En función del modo de funcionamiento 
y cableado, los requisitos de seguridad 
que se citan más abajo son factibles en 
grado máximo. 
Las especifi caciones son aplicables 
únicamente si se precisa la función de 
seguridad al menos una vez cada 6 
meses. Todas las pruebas diagnósticas se 
realizarán como muy tarde antes de la si-
guiente petición. Se adopta el tiempo de 
misión (TM) del intervalo de prueba (PTI). 
Índices de fallo de los componentes 
según SN29500.
Drawings
Zeichnungen
Schémas Disegni Gráfi cos
Circuit Diagram / Anschlussdiagramm / Schema des connexions 
Diagramma circuitale / Diagrama de circuitos
Connections / Anschlüsse / Connexions / Connessioni / Conexiones
S11, S21
S12, S22
A1-S34
S11-S34
S21-S34
A1-Y2
A1-Y41
Pulse train output / Taktausgänge / Sortie train d‘impulsions / Uscite impulsi / salidas temporizadas 
Input contacts / Eingangskontakte / Contacts d‘entrée / Contatti d‘ingresso / Contactos de entrada
Reset switch / Reset Schalter / Commutateur réarmement / Comando reset / Interruptor de reset (reinicio)
Automatic reset, startup test disabled / Automatischer Reset, ohne Anlauftest / Réarmement automatique, test au démarrage désactivé / Ripristino automatico, senza test d‘avviamento / Reset 
automático, sin test de arranque
Automatic reset, startup test enabled / Automatischer Reset, mit Anlauftest / Réarmement automatique, test au démarrage activé / Ripristino automatico, con test d‘avviamento / Reset automáti-
co, con test de arranque 
Monitoring circuit / Rückführkreis / Boucle de réarmement / Anello di retroazione / Lazo de realimentación
Cross fault monitoring disabled / Ohne Querschlussüberwachung / Contrôle croisé des défauts désactivé / Senza controllo incrociato di guasti / Sin monitorización de fallos cruzados
Technical Support / Technische Unterstützung / Assistance technique / Assistenza tecnica / Asistencia técnica
ENGLISH
DEUTSCH
FRANÇAIS
ITALIANO
ESPAÑOL
PORTUGUÊS
POLSKI
ČESKY
SVENSKA
NEDERLANDS
БЪЛГАРСКИ
EESTI
SUOMI
ΕΛΛΗΝΙΚΆ
MAGYAR
ÍSLENSKA
LATVIEŠU VALODA
LIETUVIRŠKAI
MALTI
NORSK
ROMÂNĂ
SLOVENSKY
SLOVENŠČINA
TÜRKÇE
Installation of this product must not take place until the installer has obtained a copy of the manufacturer’s instructions in a language which he can understand. This instruction sheet is available in multiple languages at http://rockwellautomation.com/literature.
Dieses Produkt darf erst installiert werden, wenn der Installateur eine Kopie der Instruktionen des Herstellers in der Sprache eingeholt hat, die er versteht. Diese Instruktionen sind mehrsprachig erhältlich unter: http://rockwellautomation.com/literature.
Ce produit ne peut être installé avant l’obtention d’un duplicata des instructions du fabricant dans une langue compréhensible. La fi che d’instructions est disponible en plusieurs langues depuis le lien http://rockwellautomation.com/literature.
Non si deve procedere all’installazione di questo prodotto fin quando l’installatore non abbia ottenuto una copia delle istruzioni del produttore in una lingua che l’installatore possa capire. La presente scheda di istruzioni è disponibile in linguaggi multipli sul sito web http://rockwellautomation.com/literature.
Absténgase de instalar este producto a menos que el instalador disponga de un ejemplar de las instrucciones del fabricante en un idioma que pueda comprender. En http://rockwellautomation.com/literature puede encontrar esta hoja de instrucciones en varios idiomas.
A instalação deste produto não pode ser efectuada até que o montador tenha obtido uma cópia das instruções do fabricante numa língua que ele compreenda. Essa folha de instruções está disponível em diversas línguas em http://rockwellautomation.com/literature.
Nie należy przeprowadzać instalacji tego produktu aż do otrzymania przez montera instrukcji producenta w języku, który on rozumie. Te karty z instrukcjami są dostępne w wielu językach na: http://rockwellautomation.com/literature.
Instalace tohoto výrobku nesmí proběhnout, dokud instalující osoba neobdrží pokyny výrobce v jazyce, kterému rozumí. Tyto pokyny jsou k dispozici v několika jazycích na http://rockwellautomation.com/literature.
Denna produkt får inte installeras förrän installatören har skaff at ett exemplar av tillverkarens instruktioner på ett språk som han/hon förstår. Detta instruktionsblad fi nns på fl era språk på http://rockwellautomation.com/literature.
Het product mag pas worden geïnstalleerd wanneer de monteur beschikt over een exemplaar van de instructies van de fabrikant in een voor hem begrijpelijke taal. Dit instructieblad is in diverse talen verkrijgbaar op http://rockwellautomation.com/literature.
: http://rockwellautomation.com/literature
: http://rockwellautomation.com/literature
http://rockwellautomation.com/literature
Това устройство не трябва да се монтира, докато монтажника не разполага с инструкциите на производителя, на разбираем за него език. Инструкциите за монтаж ще намерите на различни езици в http://rockwellautomation.com/literature.
Selle toote installatsioon ei tohi toimuda enne kui installeerija on omandanud koopia tootja instruktsioonidega keeles mida ta ise valdab. Instruktsioonid erinvates keeltes on saadaval siin: http://rockwellautomation.com/literature.
Tämä tuote voidaan asentaa vasta kun asentaja on hankkinut valmistajan ohjeet kielellä, jota hän ymmärtää. Erikieliset ohjeet ovat ladattavissa sivustolta http://rockwellautomation.com/literature.
Εγκατάσταση του προϊόντος αυτού δεν πρέπει να γίνει πριν ο εγκαταστάτης προμηθευθεί αντίτυπο οδηγιών του κατασκευαστή σε γλώσσα που ο ίδιος καταλαβαίνει. Το εγχειρίδιο αυτό διατίθεται σε διόφορες γλώσσες στη διεύθυνση http://rockwellautomation.com/literature.
Ez a termék csak akkor helyezhető üzembe, ha az üzembehelyezést végző személy rendelkezésére áll a gyártó használati utasítása az általa ismert nyelven. Az utasítás több nyelven megtalálható itt: http://rockwellautomation.com/literature 
Uppsetning á þessari vöru má ekki eiga sér stað fyrr en sá sem annast uppsetninguna hefur fengið afrit af leiðbeiningum framleiðanda á því tungumáli sem hann þekkir. Leiðbeiningarpésinn er tiltækur á mörgum tungumálum og er hægt að nб н hann hér: http://rockwellautomation.com/literature
Šī ražojuma uzstādīšanu nedrīkst veikt, pirms uzstādītājs nav saņēmis ražotāja instrukcijas tādā valodā ko viņš saprot. Šo instrukciju lapiņu var saņemt daudzās valodās no vietnes http://rockwellautomation.com/literature
Šito produkto įrengimas negali būti vykdomas tol, kol įrengėjas neturės gamintojo instrukcijų kopijos ta kalba, kurią jis supranta. Instrukciją galima rasti įvairiomis kalbomis tinklapyje http://rockwellautomation.com/literature
L-installazzjoni ta’ dan il-prodott mgħandux isir qabel ma l-installatur jakwista kopja tal-istruzzjonijiet tal-manifattur f’lingwa li tista’ tiftiehem. Il-karta tal-istruzzjonijiet hija disponibbli f’ħafna lingwi f’http://rockwellautomation.com/literature.
Dette produktet må ikke installeres før installatøren har bruksanvisningen på et behersket språk. Dette instruksjonsarket kan fås i fl ere språk på http://rockwellautomation.com/literature.
Produsul nu trebuie să fi e instalat până când cel care instalează produsul nu a obţinut o copie a manualului de utilizare , în limba pe care o poate înţelege. Aceste instrucţiuni sunt valabile în mai multe limbi la adresa http://rockwellautomation.com/literature.
Inštalácia tohto výrobku nesmie prebehnúť, dokiaľ inštalujúca osoba nedostane pokyny výrobca v jazyku ktorému rozumie. Tieto pokyny sú k dispozícii v niekoľkých jazykoch na http://rockwellautomation.com/literature.
Tega izdelka se ne sme nameščati, če si oseba, ki ga namešča, ni priskrbela izvoda proizvajalčevih navodil v jeziku, ki ga razume. Ta list z navodili v številnih jezikih je na razpolago na http://rockwellautomation.com/literature.
Bu ürünün kurulmasının, ürünü kuracak kişinin üreticinin hazırladığı talimatların bir kopyasını, ki bu talimatlar bu kişinin anlayacağı bir dilde olacaktır, elde edene kadar gerçekleşmemesi gerekir. Bu talimatlar pek çok dilde şu web-sayfasında mevcuttur: http://rockwellautomation.com/literature
Installation
Installation
Installation
Installazione
Instalación
Mount in enclosure to a min. of IP54. 
Einbau in Gehäuse nach min. IP54. 
Monter dans un coff ret conforme au minimum à la norme IP54. 
Montare in cabina con una protezione minima pari a IP54. 
Montar en envolvente a un mínimo de IP54.
Removable terminals (‘P’ versions only)
To remove, insert screwdriver and slowly move as shown.
Abnehmbare Klemmen (nur bei ‘P’- Ausführungen)
Zum Abnehmen der Klemmen, Schraubendreher langsam wie dargestellt einsetzen.
Bornes amovibles (disponibles sur versions P uniquement)
Pour démonter, insérer le tournevis et lui donner un léger mouvement comme il est indiqué.
Terminali amovibili (soltanto versioni ‘P’)
Per la rimozione, inserire il cacciavite e muovere lentamente come indicato.
Terminales extraíbles (sólo versiones ‘P’)
Para retirar, coloque un destornillador y muévalo lentamente como se indica.
mm (in)
LED Indication / LED Anzeigen / Voyants / Indicazioni ai LED / Indicadores LED
PWR
CH1
CH2
Supply voltage on / Versorgungsspannung ein / Module sous tension / Sotto tensione / Voltaje de alimentación activado
green, when safety output channel 1 is activated / grün, wenn Sicherheitsausgang Kanal 1 aktiv / verte lorsque le canal 1 des sorties de sécurité est activé / verde, quando il 
canale 1 dell‘uscita di sicurezza è attivato / verde, cuando el canal 1 de salida de seguridad está activado
green, when safety output channel 2 is activated / grün, wenn Sicherheitsausgang Kanal 2 aktiv / verte lorsque le canal 2 des sorties de sécurité est activé / verde, quando il 
canale 2 dell‘uscita di sicurezza è attivato / verde, cuando el canal 2 de salida de seguridad está activado
1
Operation time (day, hour), Betriebszeit (Tag, Stunde) / Durée de service en (jours, heures) / Giorno/ora di durata dell’operazione / Tiempo operativo (día, hora)
2
Cycle time (hour, sec), Anforderungsrate (Stunde, Sek) / Temps de cycle (heure, sec) / Ora/sec di tempo di ciclo / Tiempo de ciclo (hora, seg)
Safety Specifi cation
Sicherheitsbezogene
Spezifi kation
Spécifi cations liées 
à la sécurité
Specifi ca relativa 
alla sicurezza
Especifi caciones 
de seguridad
Dual channel e-stop, dual channel delayed outputs, monitored manual reset, output monitoring / Not-Halt zweikanalig, überwachter Reset, zweikanalige verzögerte Schützansteuerung mit Rückführkreisüberwachung /
Arrêt d‘urgence bicanal, sorties temporisées bicanal, réarmement manuel contrôlé, contrôle des sorties / Arresto d‘emergenza a canale doppio, uscite a canale doppio ritardato, ripristino monitorato manuale, uscita monitorata / 
Parada de emergencia bicanal, salidas bicanales retardado, reset manual monitorizado, salida monitorizada
Single channel gate interlock, single channel output, automatic reset, no output monitoring / Schutztürüberwachung, automatischer Reset, einkanalige verzögerte Schützansteuerung ohne Rückführkreisüberwachung /
Verrouillage porte monocanal, sortie monocanal, réarmement automatique / Interblocco barriera a canale singolo, uscita a canale singolo ritardata, ripristino automatico, senza monitoraggio d‘uscita / Conmutador puerta 
monocanal, salida monocanal retardada, reset automático, sin monitorización de salida
Application examples / Anwendungsbeispiele / Exemples d‘applications / Esempi di applicazione / Ejemplos de aplicación
Delay (s)
Y11
Y12
Y13
Delay (s)
Y11
Y12
Y13
Delay (s)
Y11
Y12
Y13
0
–
–
–
8
S21
S11
–
50
–
S21
S21
0.5
S11
–
–
10
–
S11
S21
60
S11
S11
S11
1
–
S11
–
12
S21
–
S11
80
S11
S11
S21
1.5
–
–
S11
15
–
S21
S11
100
S11
S21
S11
2
S21
–
–
18
S11
S11
–
120
S11
S21
S21
3
–
S21
–
21
S11
–
S11
160
S21
S11
S11
4
–
–
S21
26
–
S11
S11
200
S21
S11
S21
5
S11
S21
–
30
S21
S21
–
250
S21
S21
S11
6
S11
–
S21
40
S21
–
S21
300
S21
S21
S21
Wiring Examples / Schaltungsbeispiele / Exemples de 
câblages / Esempi di cablaggi / Ejemplos de conexión
TM (PTI) [a]
20
dop [d] / hop [h]
1
365 / 24
tcycle [h]/[s]
2
8 / 28,800
Dual channel, monitored manual reset, cross fault monitoring, no startup test
Zweikanalig, überwachter Reset, querschlussicher, ohne Anlauftest
Bicanal, réarmement manuel contrôlé, contrôle croisé des défauts, pas de test au démarrage
Canale doppio, ripristino monitorato, controllo incrociato di guasti, senza test d‘avviamento
Dos canales, reset monitorizado, monitorización de fallos cruzados, sin test de arranque
Single channel, monitored manual reset, no cross fault monitoring, no startup test
Einkanalig, überwachter Reset, nicht querschlussicher, ohne Anlauftest
Monocanal, réarmement manuel contrôlé, pas de contrôle croisé des défauts, pas de test au démarrage
Canale singolo, ripristino monitorato, senza controllo incrociato di guasti, senza test d‘avviamento
Uno canale, reset monitorizado, sin monitorización de fallos cruzados, sin test de arranque
Dual channel, automatic reset, cross fault monitoring, no startup test
Zweikanalig, automatischer Reset, querschlussicher, ohne Anlauftest
Bicanal, réarmement automatique, contrôle croisé des défauts, pas de test au démarrage
Canale doppio, ripristino automatico, controllo incrociato di guasti, senza test d‘avviamento
Dos canales, reset automático, monitorización de fallos cruzados, sin test de arranque
Single channel, automatic reset, no cross fault monitoring, no startup test
Einkanalig, automatischer Reset, nicht querschlussicher, ohne Anlauftest
Monocanal, réarmement automatique, pas de contrôle croisé des défauts, pas de test au démarrage
Canale singolo, ripristino automatico, senza controllo incrociato di guasti, senza test d‘avviamento
Uno canale, reset automático, sin monitorización de fallos cruzados, sin test de arranque
Dual channel, monitored manual reset, no cross fault monitoring, no startup test
Zweikanalig, überwachter Reset, nicht querschlussicher, ohne Anlauftest
Bicanal, réarmement manuel contrôlé, pas de contrôle croisé des défauts, pas de test au démarrage
Canale doppio, ripristino monitorato, senza controllo incrociato di guasti, senza test d‘avviamento
Dos canales, reset monitorizado, sin monitorización de fallos cruzados, sin test de arranque
Dual channel, automatic reset, no cross fault monitoring, startup test
Zweikanalig, automatischer Reset, nicht querschlussicher, mit Anlauftest
Bicanal, réarmement automatique, pas de contrôle croisé des défauts, test au démarrage
Canale doppio, ripristino automatico, senza controllo incrociato di guasti, con test d‘avviamento
Dos canales, reset automático, sin monitorización de fallos cruzados, con test de arranque
Dual channel, automatic reset, no cross fault monitoring, no startup test
Zweikanalig, automatischer Reset, nicht querschlussicher, ohne Anlauftest
Bicanal, réarmement automatique, pas de contrôle croisé des défauts, pas de test au démarrage
Canale doppio, ripristino automatico, senza controllo incrociato di guasti, senza test d‘avviamento
Dos canales, reset automático, sin monitorización de fallos cruzados, sin test de arranque
Single channel, automatic reset, no cross fault monitoring, startup test
Einkanalig, automatischer Reset, nicht querschlussicher, mit Anlauftest
Monocanal, réarmement automatique, pas de contrôle croisé des défauts, test au démarrage
Canale singolo, ripristino automatico, senza controllo incrociato di guasti, con test d‘avviamento
Uno canale, reset automático, sin monitorización de fallos cruzados, con test de arranque
Safety mat, monitored manual reset, cross fault monitoring, no startup test
Schaltmatte, überwachter Reset, querschlussicher, ohne Anlauftest
Tapis de sécurité, réarmement manuel contrôlé, contrôle croisé des défauts, pas de test au démarrage
Tappeto di sicurezza, ripristino monitorato, controllo incrociato di guasti, senza test d‘avviamento
Alfombra de seguridad, reset monitorizado, monitorización de fallos cruzados, sin test de arranque
Safety mat, automatic reset, cross fault monitoring, no startup test
Schaltmatte, automatischer Reset, querschlussicher, ohne Anlauftest
Tapis de sécurité, réarmement automatique, contrôle croisé des défauts, pas de test au démarrage
Tappeto di sicurezza, ripristino automatico, controllo incrociato di guasti, senza test d‘avviamento
Alfombra de seguridad, reset automático,monitorización de fallos cruzados, sin test de arranque
EN ISO 13849-1
IEC 61508 / IEC 62061
PL
e
SIL
3
MTTFd [a]
900
PFH [1/h]
7,8E-10
Cat.
4
HFT
1
DC avg.
90-99 %
DC
90-99 %