Line to line, Figure 7 - line to line configuration, Completing terminations – Rockwell Automation 1608N MiniDySC User Manual, 12-50 Amp User Manual
Page 11: Figure 8, Figure 7

Rockwell Automation Publication 1608N-UM002B-EN-P - May 2014
11
Installation
Chapter 1
Line to Line
MiniDySC L-L models must be connected as in
to operate properly.
Figure 7 - Line to Line Configuration
Completing Terminations
Output terminals are marked X1 and N or X1 and X2. If multiple loads are
served by the MiniDySC a separate distribution box must be provided. Only one
conductor should be terminated in each MiniDySC terminal block position.
Terminal torque requirements are shown in
, and
.
Figure 8 - 12 and 25 Amp Standard Ride-through (SR)
25A ER
50A SR/ER
GR
X2
X1
L2
L1
GR
L1
L2
X2
X1
GR
X2
X1
L2
L1
12A-25A SR
INPUT SOURCE
User Supplied
Circuit Breaker
L1
L2
GND
GROUND
STUD
OUTPUT TO LOADS
X1
X2
GND
X1
X2
L2
L1
L-L
Terminal Block Configurations
TERMINAL BLOCK
INPUT/OUTPUT TERMINAL RATING:
22-8 AWG (0.5-6mm2)
TORQUE: 7.1-8.9 lb-in.
(0.8-1.0 N-m)
WIRE STRIP LENGTH: .47" [12mm]
LINE TO LINE
LINE TO NEUTRAL
#10-32 GROUND STUD
TORQUE: 29 in-lb.
(3.3 N-m)
OR
FUSE
L1-N-N-X1-GR
L1-L2-X1-X2-GR