Page 11
 
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
11
Bulletin 1606 Switched Mode Power Supplies
13. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. A detailed EMC report is available upon request. 
EMC Immunity
Generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
Contact discharge 
Air discharge 
8kV 
8kV 
Criterion A 
Criterion A 
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines 
Output lines 
4kV 
2kV 
Criterion A 
Criterion A 
Surge voltage on input
EN 61000-4-5
L N 
N PE, L PE 
2kV 
4kV 
Criterion A 
Criterion A 
Surge voltage on output
EN 61000-4-5
+ - 
+ PE, - PE 
500V 
2kV 
Criterion A 
Criterion A 
Conducted disturbance
EN 61000-4-6
0.15-80MHz
10V
Criterion A
Mains voltage dips
EN 61000-4-11
0% of 100Vac 
40% of 100Vac 
70% of 100Vac 
0% of 200Vac
40% of 200Vac 
70% of 200Vac 
0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 
Criterion A 
Criterion C 
Criterion A 
Criterion A 
Criterion A 
Criterion A 
Voltage interruptions
EN 61000-4-11
0Vac, 5000ms
Criterion C
Input voltage swells
Rockwell Automation internal standard
300Vac, 500ms
Criterion A
Powerful transients
VDE 0160
over entire load range
750V, 1.3ms
Criterion A
Criteria: 
A: Power supply shows normal operation behavior within the defined limits. 
C: Temporary loss of function is possible. Power supply may shut down and restart by itself. The power supply will incur no damage or hazard.
EMC Emission
Generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22
Class B, input lines
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
Not applicable below 75W 
input power 
Voltage fluctuations, flicker
EN 61000-3-3
fulfilled
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesirable operation. 
Switching frequency
Constant, typ. 65kHz