Efficiency and power losses – Rockwell Automation 1606-XLP15A Power Supply Reference Manual User Manual

Page 8

Advertising
background image

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

8

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

8. Efficiency and Power Losses

AC 100V

AC 120V

AC 230V

Efficiency

typ.

75.8%

76.8%

77.2%

at 5V, 3A (full load)

Power losses

typ.

0.2W

0.3W

0.6W

at 0A

typ.

2.3W

2.3W

2.4W

at 5V, 1.5A (half load)

typ.

4.9W

4.6W

4.5W

at 5V, 3A (full load)

Fig. 8-1

Efficiency vs. output current at 5V,
typ.

Fig. 8-2 Losses vs. output current at 5V,

typ.

Efficiency

0

71

72

73

74

75

76

77

70

78%

3.0A

1.0

1.5

2.5

Output Current

0.5

2.0

a) 100Vac

b) 120Vac
c) 230Vac

b

c

a

Power Losses

0

0.5

3.0A

0

2

3

5W

4

1.0

1.5

2.0

Output Current

2.5

a) 100Vac
b) 120Vac

c) 230Vac

b

c

a

1

c

b

a

Fig. 8-3

Efficiency vs. input voltage at 5V, 3A,
typ.

Fig. 8-4 Losses vs. input voltage at 5V, 3A,

typ.

Efficiency

85

120

155

190

225 260Vac

72

73

74

75

76

77

78%

Input Voltage

Power Losses

3.75

4.25

4.50

4.75

5W

85

120

155

190

225 260Vac

Input Voltage

4.00