Bulletin 1336 PLUS, 1336 IMPACT, and 1336 FORCE

NEMA Type 4/12 Gasket Kit

1–3

Bulletin 1336–5.87 – November, 1997

The Bulletin 1336 PLUS, 1336 IMPACT, or 1336 FORCE Hardware
User Manual provides general installation requirements and
connection procedures. In addition to those procedures, you should
note the following before installing the Gasket Kit:

When locating the drive, allow a minimum clearance from other
components of 101.6mm (4.0in) on the top and bottom, and
50.8mm (2.0in) on either side.

With the heatsink exposed to the ambient air, the drive dissipates
heat as listed under User/Customer Supplied Enclosures. Refer to
the Drive User Manual, Appendix – Specifications/General.

When mounting the drive, ensure that the heatsink fins are
vertical.

Refer to your 1336 PLUS, 1336 IMPACT, or 1336 FORCE User
Manual for internal heat dissipation data.

For all ratings, you must verify that the selected enclosure
dissipates the total BTUs generated within the enclosure without
letting the internal ambient rise above 50

°

C. Enclosure

mounting must let the heatsink extend outside the enclosure.

Refer to Figures 1.1 through 1.6 for information on heatsink
protrusion, cutout, and drilling plans.

Before Installing the
Gasket Kit

Advertising