User Configurable Items
User Configurable Items
UPS settings
Settings are adjusted through PowerChute
 software or optional Network Management Card.
Function
Factory
Default
User Selectable
Choices
Description
Automatic
Self-Test
Every 14 days 
(336 hours)
• Every 7 days
(168 hours)
• On start up only
• No self-test
Set the interval at which the UPS will execute a 
self-test.
UPS ID
UPS_IDEN
Up to eight characters 
(alphanumeric)
Uniquely identify the UPS (i.e. server name or 
location) for network management purposes.
Date of Last
Battery
Replacement
Manufacture 
Date
mm/dd/yy
Reset this date when you replace the battery 
module.
Minimum Capacity 
Before Return from 
Shutdown
0 percent
• 0%
• 15%
• 30%
• 45%
• 60%
• 75%
• 90%
Specify the percentage to which batteries will 
be charged following a low battery shutdown 
before powering connected equipment.
Voltage Sensitivity
High sensitivity
High sensitivity
Medium sensitivity
Low sensitivity
The UPS detects and reacts to line voltage 
distortions by transferring to battery operation 
to protect the connected equipment.
In situations of poor power quality, the UPS 
may frequently transfer to battery operation. If 
the connected equipment can operate normally 
under such conditions, reduce the sensitivity 
setting to conserve battery capacity and service 
life.
Alarm Delay
Control
Enable
• Enable
• Mute
• Disable
Mute ongoing alarms or disable all alarms 
permanently.
Shutdown Delay
90 seconds
• 0 s
• 90 s
• 180 s
• 270 s
• 360 s
• 450 s
• 540 s
• 630 s
Set the interval between the time when the UPS 
receives a shutdown command and actual 
shutdown.