Rockwell Automation 1609-U500 Industrial Uninterruptible Power Supply User Manual
Page 8
 
9
User Configurable Items
Low Battery
Warning
2 minutes
2, 5, 8, 11, 14, 
17, 20, 23 minutes
PowerChute software interface provides 
automatic, unattended shutdown when 
approximately two minutes of battery operated 
run time remains.
The low-battery warning beeps are continuous 
when two minutes of run time remain.
Change the low battery warning interval setting 
to the time that the operating system or system 
software requires to safely shut down.
Synchronized
Turn-on Delay
0 seconds
• 0 s
• 60 s
• 120 s
• 180 s
• 240 s
• 300 s
• 360 s
• 420 s
Specify the time the UPS will wait after the 
return of utility power before start up (to avoid 
branch circuit overload).
High Transfer Point
120 V models: 
127 VAC
230 V models: 
253 VAC
• 127 VAC
• 130 VAC
• 253 VAC
• 257 VAC
• 133 VAC
• 136 VAC
• 261 VAC
• 265 VAC
To avoid unnecessary use of the battery where 
utility voltage is chronically high, set the high 
transfer point higher if the connected 
equipment can tolerate this condition.
Low Transfer Point
120 V models: 
106 VAC
230 V models: 
208 VAC
• 97 VAC
• 100 VAC
• 196 VAC
• 200 VAC
• 103 VAC
• 106 VAC
• 204 VAC
• 208 VAC
To avoid unnecessary use of the battery where 
utility voltage is chronically low, set the low 
transfer point lower if the connected equipment 
can tolerate this condition.
The 1609-U500E ships ready for 230 V 
sources. When operating the UPS in 208 V 
applications, the UPS low transfer voltage 
settings are adjusted through PowerChute 
software or the Network Management Card. 
The proper setting for low transfer voltage is 
196 V. 
Refer to the PowerChute user guide or the 
Network Management Card instructions for 
setting adjustment details.
Output Voltage
230 V models
230 VAC
• 220 VAC
• 230 VAC
• 240 VAC
230 V models only: Sets the output voltage of 
the UPS while operating on battery.
Function
Factory
Default
User Selectable
Choices
Description