Rockwell Automation 931S-P1C2D-DC Active Converter, Universal RTD User Manual
Page 10
Advertising
4.
Mounting
The signal conditioners are mounted on standard TS 35 rails.
5.
The electrical connection
Terminal assignment
1 input RTD +
2 input –
3 input RTD –
4 input sense +
5 not assigned
6 not assigned
7 output 0/4…20 mA
8 output 0…10 V
9 output GND
10 Supply voltage + 24 Vdc (cross-connected)
11 Supply voltage 0 V (cross-connected)
12 not assigned
Connection cross-section max. 2,5 mm
2
Multi-wire connection max. 1 mm
2
(two wires with the same cross-section)
5.1 Technical Data
Supply voltage
18 ... 30 Vdc/approx. 1 W
Operating temperature
0 °C ... +55 °C
Voltage supply via cross-connections
Current carrying capacity of the cross-connection
Յ 2 A
7 8
10
1 2 3
9
11
12
4
5
6
10