3 specifications – Rockwell Automation 931U-C9C7C-BC Configurator Software User Manual
Page 18

Page | 18
4.3 Specifications
Input types
Thermocouple
Range ‐200...+1820 °C
Types B, E, J, K , L, N, R, S, T to IEC 60584 plus custom specific
RTD
2, 3, 4 wire, within the range ‐200...+850 °C, for Pt100, Pt1000 to
IEC 60571 and for Ni100 / Ni1000 to DIN 43760, for Cu10 and,100 plus
custom specific
Potentiometer
10 Ω...100 kΩ
Resistance
10 Ω...5 kΩ
Frequency
2 Hz...100 kHz
Voltage
within the range ‐200...600 mV (min span 4 mV),
within the range ‐20...50 V DC (min span 0.5 V)
Current
within the range ‐20...50 mA (min span 1 mA)
Current Loop supply
+24 V DC
Sensor break output
Selectable between ‐2% and 102% output
Analog Output
DC voltage
0...5, 1...5, 0...10, 2...10 V or span‐settable between ‐10...10 V
(min span 2.5 V)
DC current
0...20, 4...20, 0...10 mA, or span‐settable between 0...20 mA
(min span 5 mA)
Max load (current / voltage)
700 Ω / >10 kΩ (>20 kΩ for ‐10 V…+10 V)
Action
Direct or Inverted Operation
Digital Output Relay
Relays
2 x SPCO
Max voltage and current AC
250 V AC / 2 A
Max voltage and current DC
30 V DC / 2 A
General Data
Rated voltage
24...240 V AC/DC
24…36 V AC / 24…50 V AC (ATEX Zone 2)