Figure 12 - touch screen calibration, Figure 13 - set system date and time – Rockwell Automation 1608P ProDySC User Manual, 25 and 50 A User Manual
Page 20

20
Rockwell Automation Publication 1608P-UM001A-EN-P - July 2013
Chapter 5
Display Screen
Note: To recalibrate from any screen, hold anywhere on the screen for 10 seconds. You will see a
small progress bar at the bottom of the screen. When the progress bar reaches 100 percent, the
calibration screen will open.
Step 3:
The "Touch Screen
Calibration" screen will then appear
(See
). Press and hold on the
center of the touch target, release when
the touch target begins to flash. Repeat
with the next two touch targets.
Step 4:
The screen uses the new
calibration configuration. You can test
the calibration before saving by
pressing anywhere on the screen to
ensure the touch target appears where
you press. After testing, press the
"SAVE" button. Press the "BACK"
button to return to the "System
Configuration" screen.
Figure 12 - Touch Screen Calibration
Step 5:
Set date and time by pressing
"SET SYSTEM CLOCK" in "System
Configuration." Press “SAVE” when
completed.
Figure 13 - Set System Date and Time