Voltage sag rms voltage charts, Figure 22 - rms voltage charts, Voltage sag notification – Rockwell Automation 1608M MegaDySC User Manual, 400 A User Manual
Page 33: Figure 23 - voltage sag detected

Rockwell Automation Publication 1608M-UM001A-EN-P - September 2013
33
Display Screen
Chapter 6
Voltage Sag RMS Voltage
Charts
The line and load RMS voltage (L-N) of each phase is recorded for 8 cycles prior
to the start of the voltage sag followed by the first 300 cycles of the voltage sag
(See
). Reach this screen by pressing “CHARTS” on the “Voltage Sag
Detail” screen as shown in
Figure 22 - RMS Voltage Charts
Line voltage is shown in red and load voltage is shown in green. By pressing the
check boxes in the right column, you can toggle each data series Off and On as
well as enable y-axis auto-scaling.
Note: 300 cycles = 5.0 seconds at 60 Hz or 6 seconds at 50 Hz.
Voltage Sag Notification
While the voltage sag is in-progress, a flashing red box in the upper left-hand
corner will display “SAG-IN-PROGRESS.” This box will appear on every screen
until the voltage sag ends. See
.
Figure 23 - Voltage Sag Detected