5-2 Troubleshooting Guide
Safety contacts
between terminals
#13 and #14 will
not close
Safety relay SR
Bad SLS switch
SLS switch
Replace SLS switch.
No
Fault, opens or
short in SLS
cable
SLS cable
Repair or replace cable.
No
1CR jammed on
1CR for operation
Replace if necessary.
No
IC jammed on
For operation
Replace entire contactor ass’y.
No
Power circuit to
safety relay open
Power LED off
Reset power supply.
—
Failed safety
relay
LEDs during operation
Replace.
No
Safety relay 1SR
Power circuit to
safety relay open
Power LED off
Reset power supply.
No
Failed safety
relay
LEDs during operation
Replace.
No
Won’t pick up
1CR
Open coil
Flash light coil
Replace.
No
Open circuit to
coil
—
—
—
Welded contacts
—
Replace.
No
Won’t drop out
Welded contacts
—
Replace.
No
Foreign material
jam
—
Replace.
No
Table 5.A SLS Box (Continued)
Problem
Component
Possible Cause
Check
Suggested Action
Repairable?