Description of use, Preface-2 – Rockwell Automation 1000 Safety Lockout System User Manual
Page 8
 
Publication 1000-UM001B-US-P - July 2000
Preface 2
Description of Use
The SLS switch should not be used to initiate normal stopping of the system. 
The normal system stop function(s) should be used to stop the system and 
then, when necessary, the remote SLS switch can be used to initiate the 
isolation of the system. When the SLS switch is operated for the purpose of 
isolation, a white SAFE light will illuminate when the system is isolated. The 
illumination of the SAFE light is the control indication that the electrical 
power to the equipment on the machine fed through the SLS is de-energized 
and isolated.
An SLS service technician must investigate, correct and log any abnormality.
Simplified Wiring Diagram 
and Sequence of Operation 
After using the normal stop function, the machine operator can turn the SLS 
switch from the ON to the OFF position and then lock the SLS switch in the 
OFF position. This will cause the isolation contactor (IC) to drop out and arm 
the SAFE pilot light. The voltage supervision relay (VSR) will then monitor 
the load side of the isolation contactor for voltages greater than 10V and will 
monitor the position of the isolation contactor through its normally closed 
positively guided auxiliary contact. If the voltage check is OK and the IC 
auxiliary contact is closed, the VSR’s safety contacts will close, illuminating the 
SAFE pilot light.