Should a temperature measurement range be selected that is larger than
the specified range of the thermocouple used, then the module sets itself
to the maximum specified range:

Type K

–200º C … +1372º C

Type J

–200º C … +1200º C

Type T

–200º C … +400º C

Type E

–200º C … +1000º C

Type N

–200º C … +1300º C

Type R

–50º C … +1760º C

Type S

–50º C … +1760º C

Type B

+50º C … +1820º C

The voltage output and the combined current output (0…20 mA and
4…20 mA) are routed from two separate, calibrated connections.
The output selected via the DIP switch, is the only output that is calibrated.